1) GENERAL OUTLINE
Motor-driven header for automatic sliding doors with one leaf (mod. VISTA SL
A200 SMART 1) or two (mod. VISTA SL A200 SMART 2).
Complete with control panel. Accessories available for producing a complete
installation.
For VISTA SL A200 SMART 1 models the door will be delivered with the actual
door opening PU on the left (looking at the door from the inside) (Fig. AI) .
2) TECHNICAL SPECIFICATIONS
MECHANICAL SPECIFICATIONS
Single-leaf doorway
min 750mm max 2150mm
opening
Double-leaf doorway
min 800mm max 2900mm
opening
Single-leaf capacity load
200 kg
Double-leaf capacity load 150+150 kg
Protection rating
IP X0
Crosspiece dimensions
See Fig. D
ELECTRICAL SPECIFICATIONS
220-230V~, 50/60Hz
Power supply
110-120V~, 50/60Hz
Rated power
300 W
Fuses
see Fig. Q
Accessories power supply 31.5 VDC max 500mA
Power supply V SAFE
24V max 30mA
Alarm output and door
Contact max 24V 0,5A
status
1-LEAF: Adjustable up to 1 m/s
Opening/closing speed
2-LEAF: Adjustable up to 2 m/s
1-LEAF: In the range 5 to 10 cm/s in automatic mode
Approach speed
2-LEAF: In the range 10 to 20 cm/s in automatic mode
Temperature range
-20°C + 55°C
Operating cycle
Continuous at 25°C
Emergency batteries
(optional extras) 2 x 12V 1.2Ah
Radio-receiver built-in
Frequency 433.92 MHz
Rolling-Code
Max. n° of remotes that
63
can be memorized
Sound pressure
<70dbA
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
3) PREPARING THE ELECTRICAL SYSTEM
Prepare the electrical system (fi g. A), referring to the standards in force. Keep
mains power connections well separated from service connections (photocells,
safety edges, control devices, etc.).
Keep mains power connections well separated from safety extra low voltage
connections. Secure the power cable by means of the cable clamp located in
the transformer's cover. Connect the power cable so that the earth wire (yellow/
green) is longer than the other wires.
4) IDENTIFICATION OF COMPONENTS (Fig. AA)
In the standard composition, the automated VISTA SL A200 SMART system is made up of:
1 Load-bearing header in oxidized aluminium
2 Power supply unit complete with bipolar switch, mains fuse and noise fi lter
3 Microprocessor-based control unit ARIA - EVO
4 DC gearbox
5 Optical encoder for detecting travel and checking for obstacles
6 Driven pulley
7 Drive belt
8 2 Door runners with 2 wheels on bearings, anti-derailment wheel, height and
depth adjustable
11 Rubber hinge
12 Cable raceway
The following accessories are available to complete installation:
9/10 PRV AA SL
Leaf fastening profi le
13 WMP
Wall mount profi le
14 BBV
Battery-powered panic device
15 ERV
Electromagnetic bolt and manual release
16 VISTA SEL
Digital function pushbutton unit (optional extra)
17 SBV
Supporting beam in oxidized aluminium
18 PGI
Bottom door guide profi le for framed doors
19 PPR
Slide for bottom door guide
INSTALLATION MANUAL
20 VIO
21 FPA1
21 FPA2
22 CRTV
23 SASA1-2
PPA
5) FASTENING METHOD
- Assembling the Cover (Fig. B ).
- Cable routing (Fig. C ).
WARNING- When fastening the header, only use fl at countersunk screws
as shown in Fig. I Rif. 1 or screws with heads no more than 5 mm high. If
this condition is not met, collisions may occur with the runners.
6) DETERMINING HEADER FASTENING HEIGHT (Fig. E)
The fastening height HFT of the VISTA SL A200 SMART header must be mea-
sured where the fl oor is at its highest (Fig. E) . This is to prevent the possibility of
the moving door leaf getting stuck once installation is fi nished. Once installed,
the height of the doors can still be adjusted by means of the special adjusters
on the runners (Fig. L ).
WARNING: The VISTA SL A200 SMART header must be fastened so that
it is perfectly horizontal. This condition must be met to ensure that the
automated system operates properly.
6.1) Fastening to wall (above an opening) (Fig. F - G)
6.2) Mounting between two walls (inside door opening space) (Fig. H)
To position the header symmetrically with respect to the doorway opening, no
matter what kind of installation you are dealing with (above an opening, inside
an opening, etc.), you need to mark both the centre line of the structural opening
and centre line of the VISTA SL A200 SMART header. Fasten the VISTA SL A200
SMART header, lining up the two marks (Fig. H) .
7) POSSIBLE INSTALLATIONS
A number of installation methods for the automated system are listed below:
-
Wall mounted.
-
Ceiling mounted (with supporting beam SBV).
-
Incorporated in door frame (with or without supporting beam SBV).
7.1) Wall mounting (Fig. I)
A "support profi le" (WMP) is also available to help with wall mounting (Fig. I)
It is best to attach shims in line with the fastening holes already made in the
header. That way, the fastening points will sit on a solid base and you will avoid
the track bending while screws are being fastened. In the event fastening holes
have to be drilled in addition to those already made, drill them approx. every
600-800 mm: this will also depend on what kind of surface you are dealing with
(concrete, brick, wood, iron, etc.).
7.2) Ceiling mounting (with supporting beam SBV Fig. AB - AC)
This type of installation is particularly suitable if the door leaf and fi xed panel are
made from frameless glass, and hence are not load-bearing.
7.3) Incorporated in door frame
The supporting beam is incorporated in a load-bearing door frame or a fl at profi le
is built into the frame that must be thick enough to fasten the VISTA SL A200
SMART header securely.
8) DOOR ASSEMBLY AND ADJUSTMENT
8.1) Framed doors
Before removing the door leaf mounting profi le in order to fasten it to the actual
leaf, it is advisable to mark the position where the runners are fastened to the
door leaf mounting profi le (Fig. AI - AJ) . This will make fi nal adjustment of the
door leaves' travel limit brackets and centring of the ERV easier. If the top rail of
.
the framed door leaf is less than 6-7mm thick and the leaf is heavy (>120Kg), it
must be reinforced inside with an iron profi le or plate into which the door leaf
mounting profi le can be screwed at various points.
8.2) Glass doors (Fig. AE)
For further details, see "pliers instruction sheet"
The clamping system PPA can be used only for 10 or 12mm thick tempered
glass doors or laminated safety glass doors.
It must not be used with double glazing. For the sake of simplicity, reference is
made to glass doors from hereon in.
- No holes must be made in the sheet of glass
- Clamp PPA must be fastened to the door mounting profi le as illustrated in Fig.
AE .
- Seals G, of a suitable thickness, must be placed on both sides of the sheet of
glass, between the clamp and glass. Use only seals provided for this purpose.
9) DOOR INSTALLATION AND ADJUSTMENT
- Installing the Doors (Fig. K) .
- Adjusting the Doors (Fig. L) .
10) FLOOR-MOUNTED DOOR GUIDE (Fig. M)
- Framed doors (Fig. M Rif. 3 )
- Glass doors (Fig. AE)
- Breakout doors
See the relevant instruction manual for their assembly.
11) ADJUSTING TRAVEL LIMIT STOPS (Fig. N)
If the positions of the RH and LH travel limit stops (parts. 10 Fig. AA ) need to be fi ne-
tuned, carefully check the travel and alignment of the runners carrying the doors.
It is important to remember that the position of the travel limit stops also deter-
mine the control board's self-learning.
Automatic sliding door safety and opening sensor
Photocells (1 amplifi er, 1 transmitter, 1 receiver)
Photocells (1 amplifi er, 2 transmitters, 2 receivers)
Cover
Breakout door device.
Clamp for glass doors (Fig. AE) .
- 23