Installation and Connection
3.2.6 Cable Separation Distance
Provide separation between the control and power cables and between the control
cables (relay output cables and other control cables) as per
Inverter Output
Rated Current
3.3 INSTALLATIONS ACCORDING TO EUROPEAN DIRECTIVE OF
ELECTROMAGNETIC COMPATIBILITY
Inverters with the option C2 or C3 (CFW500...C...) feature internal RFI filter to reduce
the electromagnetic interference. Those inverters, when properly installed, meet the
requirements of the directive of the electromagnetic compatibility.
The CFW500 inverter series was developed for professional applications only.
Therefore, the emission limits of harmonic currents by the standards EN 61000-3-2
and EN 61000-3-2/A 14 are not applicable.
3.3.1 Conformal Installation
1) Inverters with option internal RFI filter CFW500...C... (with grounding switch of the
capacitors of the internal RFI filter in the position
grounding switch in
2) Shielded output cables (motor cables) with shield connected at both ends, motor
and inverter, by means of a low impedance to high frequency connection.
Maximum motor cable length and conduced and radiated emission levels according
to
table
B.3. If a lower conducted emission level and/or longer motor cable is desired,
then an external RFI filter must be used at the inverter input. For more information
(RFI filter commercial reference, motor cable length and emission levels) refer to the
table
B.3.
3) Shielded control cables, keeping the separation distance from other cables according
to
table
3.3.
4) Grounding of the inverter according to instruction of the
Connections.
5) Grounded power supply.
18 | CFW500
Table 3.3: Cable separation distance
of the cable(s)
≤ 100 m (330 ft)
≤ 24 A
> 100 m (330 ft)
figure
A.2.
table
Minimum
Length
Separation
Distance
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
). Check the location of the
- English -
3.3.
item 3.2.4 Grounding