Technische Daten
Isolationskoordination (IEC 60664-1/IEC 60664-3)
Bemessungsspannung ..........................................................AC, 250 V
Überspannungskategorie (OVC) ........................................................III
Bemessungs-Stoßspannung (IEC 60664-1) .................................... 4 kV
Versorgungsspannung
Versorgungsspannung U
......................................... AC/DC 24...240 V
s
Frequenzbereich von U
.............................................DC, 50...400 Hz
s
Messbereiche
Messbereich Isolationsfehlersuche (I
EDS440: ....................................................... 1,5...25 mA (DC, 50 mA )
EDS441: .............................................................................0,15...5 mA
Bemessungs-Frequenzbereich ............................DC, 16 2/3...1000 Hz
Messbereich Differenzstrommessung (I
EDS440: ..............................................100 mA...20 A, (50...1000 Hz)
EDS441: ....................................................100 mA...2 A, (50...60 Hz)
Schnittstellen
Schnittstelle/Protokoll ....................................RS-485/BS/Modbus RTU
Schaltglieder
Bemessungsbetriebsspannung ...............................................250 VAC
Bemessungsbetriebsstrom ..............................................................7 A
Bemessungsisolationsspannung .................................................... 4 kV
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ............. AC-13/AC-14/DC-12/DC-12/DC-12/DC-12
Bem.betriebsspannung ................230 V/230 V/24 V/48 V/110 V/220 V
Bem.betriebsstrom ...................................5 A/3 A/1 A/1 A/0,2 A/0,1 A
Bemessungsisolationsspannung ≤ 2000 m NN ..........................250 V
Bemessungsisolationsspannung ≤ 3000 m NN ...........................160 V
Minimale Kontaktbelastbarkeit ........................ 1 mA bei AC/DC ≥10 V
Sonstiges
EMV ................................................................................IEC 61326-2-4
Schutzart Einbauten (DIN EN 60529) .............................................IP40
Schutzart Klemmen (DIN EN 60529) ............................................. IP20
Normen
DIN VDE 0100-410 (VDE 0100-410)
DIN EN 61557-9 (VDE 0413-9)
IEC 61557-9
DIN EN 50155 (VDE 0115-200)
DIN EN 45545-2:2016
14
)
ΔL
)
Δn
Technical data
Insulation co-ordination (IEC 60664-1/IEC 60664-3)
Rated voltge ..........................................................................AC, 250 V
Overvoltage category (OVC) ...............................................................III
Rated impulse voltage (IEC 60664-1) ............................................ 4 kV
Supply voltage
Supply voltage U
..................................................... AC/DC 24...240 V
s
Frequency range from U
............................................DC, 50...400 Hz
s
Measuring rnanges
Insulation fault location measurement range (I
EDS440: ....................................................... 1.5...25 mA (DC, 50 mA)
EDS441: ........................................................................... 0.15...5 mA
Rated frequency range ........................................DC, 16 2/3...1000 Hz
Residual current measurement range (I
EDS440: ..............................................100 mA...20 A, (50...1000 Hz)
EDS441: ....................................................100 mA...2 A, (50...60 Hz)
Interfaces
Interface/protocol .........................................RS-485/BS/ Modbus RTU
Switching elements
Rated operating voltage ..........................................................250 VAC
Rated operational current ................................................................7 A
Rated insulation voltage ................................................................ 4 kV
Contact data acc. to IEC 60947-5-1
Utilisation category .............. AC-13/AC-14/DC-12/DC-12/DC-12/DC-12
Rated op. voltage .........................230 V/230 V/24 V/48 V/110 V/220 V
Rated op. current. .....................................5 A/3 A/1 A/1 A/0.2 A/0.1 A
Rated insulation voltage ≤ 2000 m NN .......................................250 V
Rated insulation voltage ≤ 3000 m NN ......................................160 V
Minimum contact rating .....................................1 mA at AC/DC ≥10 V
Other
EMC ................................................................................IEC 61326-2-4
Degree of protection, built-in components (DIN EN 60529) ...........IP40
Degree of protection, terminals (DIN EN 60529) ............................IP20
Standards
DIN VDE 0100-410 (VDE 0100-410)
DIN EN 61557-9 (VDE 0413-9)
IEC 61557-9
DIN EN 50155 (VDE 0115-200)
DIN EN 45545-2:2016
)
ΔL
)