Menu: Cooling; Menu: Hot Water - Daikin RoCon+ HP EHSX04P30D Manual De Instrucciones

Ocultar thumbs Ver también para RoCon+ HP EHSX04P30D:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 233
7.6.4

Menu: Cooling

[→ Main menu → Configuration → Cooling]
Parameters
Setting range
Min / Max
T-Flow Cool-
5 - 25 °C
ing start
T-Flow Cool-
5 - 25 °C
ing max
Start T-Out
15 - 45 °C
Cooling
Max T-Out
20 - 45 °C
Cooling
Feed temper-
5 - 25 °C
ature lower
limit
Feed temper-
8 - 30 °C
ature cooling
mode
Cooling set-
-5.0 - +5.0 K
point adjust-
ment
Interlink tem-
1 - 50 K
perature re-
duction
Tab. 7-23 Parameter in menu: "Cooling"
7.6.5

Menu: Hot water

[→ Main menu → Configuration → DHW]
Parameters
Setting range
Min / Max
Max. hot wa-
10 – 240 min
ter loading
time
Hot water
0 – 180 min
blocking time
Hot water
2 - 20 K
hysteresis
Wait time ext.
20 - 95 min
heat gener-
ator
Circulation
pump control
Off
On
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Description
Only if [Weather-dependent] parameter = weather-compensated:
Setting of the cooling feed target temperature at the start of cooling mode
(outside temperature = [Start T-Out Cooling] parameter)
Only if [Weather-dependent] parameter = weather-compensated:
Setting of the minimum cooling feed target temperature. This is held con-
stant as of the outside temperature ([Max T-Out Cooling] parameter).
Only if [Weather-dependent] parameter = weather-compensated:
Setting as of which outside temperature cooling mode starts with the
highest cooling feed target temperature [T-Flow Cooling start] (setting con-
dition: "Cooling" operating mode).
Only if [Weather-dependent] parameter = weather-compensated:
Setting of the outside temperature at which the lowest cooling feed target
temperature [T-Flow Cooling max] is specified (setting condition: "Cooling"
operating mode).
Only if [Weather-dependent] parameter = weather-compensated:
Setting of the absolute lower limit of the cooling feed target temperature.
Limitation acts if a lower cooling feed target temperature is determined
from other parameter settings.
Only if [Weather-dependent] parameter = feed temperature, fixed
Setting of the cooling feed target temperature (fixed value) for active cool-
ing mode.
Parallel shift of the cooling characteristic curve by the set value.
Only if [Interlink function] parameter = On:
When the RT switching contact cooling is closed, the cooling feed target
temperature is reduced by the set value (see [Interlink function] parameter).
Request, e.g. by HP convector.
Description
Setting of the maximum duration of a domestic hot water preparation cycle.
Then cancellation of domestic hot water preparation if the current hot water
temperature does not reach the set target value in the [Hot water temp. set-
point 1] parameter.
Setting of the blocking time after completion or cancellation of a domestic
hot water preparation cycle. The repeat request for domestic hot water pre-
paration is operated after this blocking time has elapsed at the earliest.
Hot water charging switching threshold
Setting of the temperature difference by which the temperature in the hot
water storage tank may fall in comparison with the currently valid hot water
target temperature [Hot water temperature setpoint] before the heat pump
for hot water charging is to be activated.
Delay time as of which the additional heat generator may support the heat
pump in hot water charging (see
Setting for the control of a circulation pump. Use in France not permitted!
Optional circulation pump is synchronously controlled to the active switch-
ing time program for domestic hot water preparation.
Optional circulation pump is controlled according to the [Circulation pro-
gram] switching time program.
Chap.
4.5).
7
Parameter settings
Factory
Incre-
Access
setting
ment
BE HF
18 °C
1 °C
E
8 °C
1 °C
E
24 °C
1 °C
E
35 °C
1 °C
E
18 °C
1 °C
N
18 °C
1 °C
E
0.0 K
1 K
N
5 K
1 K
N
Factory
Incre-
Access
setting
ment
BE HF
60 min
10 min
N
30 min
10 min
N
7 K
1 K
E
50 min
1 min
E
-
E
Operating Instructions
E
E
E
E
E
E
E
E
E
E
E
E
E
43