Function
ID / Function
Terminal ID
Unique numbering of a RoCon+ B1 or
EHS157034 control panel from which a
heat generator and/or mixer module can
be remotely controlled in the RoCon
system.
The authorisation for remote control can
be allocated to up to 10 control panels
in the RoCon system. If remote control
is to be possible in the RoCon system,
the control panel must be allocated the
ID "0".
Device ID
Unique numbering of a heat generator
or mixer module in the RoCon system.
Up to 16 device numbers can be alloc-
ated.
These device numbers are detected
during a [Bus - Scan] and are displayed
for identification of a remotely controlled
device.
Tab. 4-10 Functional IDs in the RoCon system
4.8.1

Selecting the terminal address

[→ Main menu → Terminal → Address]
Setting of the terminal ID of the control panel for system access. The
set value must be unique throughout the entire system. Confirmation
of this parameter with the rotary button effects a new initialisation of
the control unit.
All settings (except "Off") authorise the user of the control panel to
activate the terminal function and thus to operate all RoCon system
components with a valid device ID.
4.8.2

Bus-Scan for terminal function

[→ Main menu → Terminal → Bus scan]
After activating the "Bus scan", a list of detected devices (with as-
signed terminal address) is displayed in the menu [→ Main menu
→ Terminal] for selection. After selecting and confirming an external
device, the terminal function for this device is activated. The control
panel is then in terminal operation.
The local control panel acts as a remote control for the external
device and the corresponding start screen is shown on the display.
In this case, all the control functions are performed and saved 1:1 in
the same way as on the external device. The displayed values and
symbols are always taken over by the selected device.
To operate the local device, switch to the start screen of the external
device. Press and hold the rotary switch to return to the menu of the
local device.
INFORMATION
To perform the bus scan, a valid terminal address must be
assigned to the RoCon+ B1 control panel of the Daikin
Altherma EHS(X/H) or the EHS157034 room station. This
can only be done with a specialist code. Contact your heat-
ing expert in this regard.
If the terminal function is to be used in the heating system,
the terminal ID = 0 must be allocated to a control panel.
Example: Activate terminal operation for the heat generator with bus
identification 2 [→ Main menu → Terminal → Bus scan]:
The bus scan is carried out. An overview of all devices that are
found is displayed.
Operating Instructions
24
System components
Parameters
Daikin Altherma EHS(X/H)
(RoCon BM2C)
EHS157034 room station
Daikin Altherma EHS(X/H)
(RoCon BM2C)
EHS157068 mixer module
[Heating circuit assign-
Comments
[Terminaladress]
Factory setting = Off
See
Chap. 7.9
The value should be set to "0" if at least 1
mixer module is connected in the RoCon sys-
tem and the mixer circuit is to be operated
from the heat generator.
[Terminaladress]
Factory setting = Off
See
Chap. 7.9
The value must be set to a unique numerical
value in the RoCon system if the room station
system components are to be remotely con-
trolled using a valid device ID.
[BUS ID HS]
Identical to heat generator detection.
See
Chap. 7.11
The value must not be the same as the HC ID
of a mixer module in the RoCon system.
Identical to the HC ID.
ment]
The value must not be the same as the heat
See
Chap. 9
generator ID of the Daikin heat generator in
the RoCon system.
The value must be the same as the setting of
the address switch.
1
Turn the rotary switch clockwise until the BM1/BE1 #2 controller
is displayed in blue.
2
Briefly press the rotary button to confirm ("OK").
è The local control panel acts as a remote control for the heat
generator with bus ID 2.
To end terminal operation and switch back to the operation of the as-
signed device, switch to the start screen of the external device.
Press and hold the rotary switch to return to the menu of the local
device.
INFORMATION
If the local control panel is used as a remote control for a
mixer module, both the standard screen and the menu
structure have been changed (see
4.9

Statistics

[→ Main menu → Statistics]
In this menu, summed values for the power output and running times
of the heat pump and its components since commissioning (or since
the last reset by a specialist) can be called up.
Chap.
9).
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN