Descargar Imprimir esta página

INFOSEC UPS SYSTEM E4 Pro One Serie Manual De Usuario página 44

Publicidad

Idiomas disponibles

Idiomas disponibles

05: Voltage range for ECO mode
Interface
06: Bypass enable/disable when UPS is off
Interface
07: Bypass voltage range setting
Interface
08: Activation/deactivation of programmable sockets
Interface
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com Hot Line Tel : +33
44
(0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 23 AA 59 204 16
Configuration
Parameter 2: Set the acceptable high voltage point and low
voltage point for ECO mode by pressing the Down or Up button.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is +7V to +24V of nominal voltage.
(Default value: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is -7V to -24V of nominal voltage.
(Default value: -12V)
Configuration
Parameter 2:
Activate or deactivate the bypass function. You can choose from
the following two options:
ENA: bypass enable
DIS: bypass disable (Default)
Configuration
Parameter 2: Set the acceptable high voltage point and the
acceptable low voltage point for bypass mode by pressing the
Down or Up button.
HLS: High bypass voltage point
For 200/208/220/230/240 VAC models :
230-264: set the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models :
170-220: set the low voltage point in parameter 3 from 170Vac to
220Vac. (Default: 170Vac)
Configuration
Parameter 2: Activate or deactivate programmable sockets.
ENA: Activate programmable sockets
DIS: Disable programmable sockets (Default)

Publicidad

loading