ELECTRICAL POWER REQUIREMENTS

grounding can result in electrical shock. The wiring should be
done by a qualified electrician.

ELECTRICAL WIRING

Refer to the air compressor's serial label for the unit's voltage and amperage
requirements. Ensure that all wiring is done by a licensed electrician, in
accordance with the National Electrical Code.

MAIN POWER PANEL

For best performance and reliable starting, the air compressor must be installed
on a dedicated circuit, as close as possible to the electrical power panel. Provide
circuit breaker or fuse protection at your main power panel. Use time delay fuses
on the circuit, because the compressor will momentarily draw several times its
specified amperage when first started.
NOTE: A circuit breaker is recommended. If the air compressor is
connected to a circuit protected by a fuse, use dual element time
delay fuses (Buss Fusetron type "T" only).

MAIN POWER DISCONNECT SWITCH

Install a main power disconnect switch in the line from the panel to the
compressor. The main power disconnect switch must be located near the
compressor, for ease of use and safety. When turned OFF, the main power
disconnect switch shuts off all power to the compressor. When turned ON, the
compressor will start and stop automatically, controlled by the pressure switch.

LOW VOLTAGE PROBLEMS

Low voltage will cause difficult starting or an overload. Low voltage can be
caused by a low supply voltage from the local power company, other equipment
running on the same line, or inadequate wiring. If any other electrical devices are
drawing from the compressor's circuit, it may fail to start.
Low voltage to the compressor can be caused by a supply wire of insufficient
gauge for the distance between the compressor and the power source. The
longer the distance, the larger the wire gauge (lower the number) must be, to
overcome the inherent voltage loss caused by the wire resistance. Refer to the
National Electrical Code to determine proper wire size for your circuit.
If the wiring is not adequate, the input voltage will drop by 20 to 40 volts at
startup. Low voltage or an overloaded circuit can result in sluggish starting that
causes the circuit breaker to trip, especially in cold conditions.

GROUNDING INSTRUCTIONS

This product must be connected to a grounded, metallic, permanent wiring
system, or an equipment - grounding terminal or lead on the product.
Risk of electrical shock. Improper electrical
10- ENG