Installation
- Pilot gas - Control panel
PILOT GAS TRAIN CONNECTION
The pilot gas train is already installed to the burner and shall be connected to
the main gas supply line preferebly with flexible pipe.
The pilot gas train is composed of n° 2 safety valves and n°1 gas governor and
filter. Max inlet pressure 1 bar.
WARNING: Pilot gas train must be connected according to the drawing of the
gas line.
GAS VALVES ADJUSTMENT
Note : the pilot valves are pre-adjusted in the factory. To increase or reduce the
gas flow act on the gas governor.
GAS GOVERNOR ADJUSTMENT
The gas governor, with built-in filter, must be installed so as
to stabilise the outlet gas pressure and to avoid that
eventual impurities reach the gas valve. To increase gas
pressure, remove the cover of governor and turn screw C.
Unscrew screw C to reduce pressure, then fit the cover.
Note: the inlet gas pressure must not be higher than the
specified max. gas pressure.
KITTC- Tightness control
Tightness control is provided as a kit and shall be
assembled into the main gas train according to the
instructions of the gas train separate manual.
KITPRES... Maximum pressure switch assembly
Maximum pressure switch is provided as a kit and
shall be assembled into the main gas train
according to the instructions of the gas train
separate manual.
KITMD-RWF40 PID regulator
All progressive burner can be turned modulationg
with the installation of the PID that regulates the
output combined with a probe.

Control panel

F
B
420010576400
Tightness control
KITTC- Model
Compulsory > 1200 kW
SAL
HLBT
0
1
0: OFF
R
1: ON
SAB
HLR
I
II
I: 1 st.
V
II: 2 nd.
SAOG
HLnafta
POS 0: STOP
R
POS 1: NAFTA
POS 2: GAS
POS 3: AUTO
SARA
HLgas
0
I
R
SA s.r
+
C
Modulation Kit
KITMD-RWF50
Probe-...
Reset Key
D
A - pulsador de desbloqueo
B - Indicador del funcionamiento
Operating lamps
rojo(Fuel pesado)
(orange=heavy oil; green=
rojo(gas)
gas; red= heater)
verde(resistencia)
C
C - conmutador:
Selector switch:
I
= potencia mínima
Operation at max. output
E
II
= potencia máxima
Operation at min. output
ON/OFF switch
D - interruptor I / O
E - conmutador:
Selector switch:
0 = Stop
0 = STOP
G
1 = Heavy oil operation
1 = funcionamiento a Fuel pesado
2 = Gas operation
2 = funcionamiento a Gas
3 = Automatic
3 = automatic
F - Indicador de bloqueo
Thermal lock-out lamp
A
G - interruptor resistencias
Switch AUX heater
Max Pressure switch
KITPRES50
KITPRES150