Ecoflam MULTIFLAM D 200.1 PAB TC GN SR 400-50 Manual De Uso página 14

Ocultar thumbs Ver también para MULTIFLAM D 200.1 PAB TC GN SR 400-50:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
Installation
Ignition electrode
Electrical connection
The electrical installation and connection
work must only be carried out by an
authorised electrical specialist.
All applicable rules and regulations must
be observed.
The electrical installation should include a
type A circuit breaker.
The applicable guidelines and
directives must be observed, as well as
the electrical circuit diagram supplied
with the burner!
• Check to ensure that the power supply
voltage is as specified in the electric
diagram and in data plate.
• Burner fuse: 5 A.
Electrical connection (plug-in)
It must be possible to disconnect the
burner from the mains using an
omnipolar shutdown device complying
with the standards in force. The burner
and heat generator (boiler) are connected
to the terminal block of the cabinet (fig.1).
Connecting the gas train
Connect the gas train to the plugs on the
burner.
The burners are produced with
connections suitable for power supply
400 V three-phase.
The burners with electric motors of an
output lower or equal to 7,5 kW can be
14
www.ecoflam-burners.com
- Electrical connection - Checks before commissioning
3 ÷ 4 mm
adapted to 220-230 V (please follow the
instructions on the backside); motors with
higher output can only work 380-400 V
three-phase.
In case of request of burners different from
the above mentioned standard, it is
recommended to make specific mention in
the order.
Instructions: how to adapt electric
motors of an output lower or equal to
7,5 kW to 220-230 V power supply
It is possible to change the voltage of the
burner by operating as follows:
1. change the connection inside the
electric box of the motor, from star to delta
(see picture 3);
2. change the setting of the thermal relay,
referring to the absorption values indicated
in the motor nameplate. If necessary,
replace the thermal relay with another one
of suitable scale.
This operation is not possible on motors
above 7.5 kW.
For more information, please contact the
Ecoflam staff.
Position of electrodes
Setting the ignition electrode: see diagram
Always check the position of the
electrodes after service or substitution
or assembly of LPG kit as wrong position
might cause ignition problem.
Checks before commissioning
The following must be checked before
initial commissioning:
5 ÷ 6 mm
• That the burner is assembled in
accordance with the instructions given
here.
• That the burner is pre-set in accordance
with the values in the adjustment table.
• Setting the combustion components.
• The heat generator must be ready for
operation, and the operating regulations
for the heat generator must be observed.
• All electrical connections must be correct.
• The heat generator and heating system
must be filled with water and the
circulating pumps must be in operation.
• The thermostats, pressure regulator, low
water detectors and any other safety or
limiting devices that might be fitted must
be connected and operational.
• The exhaust gas duct must be
unobstructed and the secondary air
system, if available, must be operational.
• An adequate supply of fresh air must be
guaranteed.
• The heat request must be available.
• Sufficient gas pressure must be
available.
• The fuel supply lines must be assembled
correctly, checked for leaks and bled.
• A standard-compliant measuring point
must be available, the exhaust gas duct up
to the measuring point must be free of
leaks to prevent anomalies in the
measurement results.
400V
230V
Flame detector system check
The control of the detector current shall be
carried out by plugging a microamperometer
with full scale at 1000 µA (D.C.) in series
with the UV-cell. If the detector current is too
low verify the connection between phase
and neutral of the burner and the grounding
of the burner itself. Minimum required detec-
tor current is 200 µA.
SW
BL
BL
SW
SW = BLACK
BL = BLU
3
1
LME22
2
QRA
420010576400

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Multiflam d 200.1 pab tl gn sr 400-50

Tabla de contenido