Installing The Ducts; Concentric Ducts; Separate Ducts - Baxi LUNA DUO-TEC MP 1.90 Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

10. INSTALLING THE DUCTS

The boiler is easy and flexible to install thanks to the extensive range of available accessories, as described below. The boiler
has been designed for connection to a vertical or horizontal coaxial flue-air duct. The boiler can also be used with separate ducts
using the accessory splitting kit.
WARNINGS
C13, C33 The terminals for separate flues must be fitted inside a 50 cm square. Detailed instructions are provided with the indi-
vidual accessories.
C53 Do not fit the flue and air duct terminals on opposite walls of the building.
C63 The maximum pressure drop ΔP of the ducts must not exceed the values indicated in table 1 (A-B). The ducts must be certi-
fied for this specific use and for a temperature in excess of 100°C. The flue terminal must be certified to EN 1856-1.
C43, C83 The flue terminal or flue duct must be suitable for the purpose.
For optimal installation, the accessories supplied by the manufacturer should be used.
TABLE 1A
If the flue and air ducts installed are not supplied by BAXI S.p.A., make sure they
are certified for the type of use and have a maximum pressure drop as indicated in
the table to the side.
To optimise operating safety, make sure the flue ducts are firmly fixed to the wall with suitable brackets.
Make sure there is a minimum downward slope of 1 cm per metre of duct towards the boiler.
SOME OUTLET DUCT INSTALLATION EXAMPLES AND THEIR RELATIVE MAXIMUM LENGTHS ARE SHOWN IN SECTION D
AT THE END OF THIS MANUAL.

10.1 CONCENTRIC DUCTS

This type of duct is used to discharge exhaust fumes and draw
combustion air both outside the building and if a LAS flue is
fitted. The 90° coaxial bend allows the boiler to be connected
to a flue-air duct in any direction as it can be rotated by 360° It
can also be used as a supplementary curve combined with a
coaxial duct or a 45° curve.
If fumes are discharged outside the building, the flue-air duct
must protrude at least 18 mm from the wall to allow an alu-
minium weathering surround to be fitted and sealed to avoid
water infiltrations.
• A 90° bend reduces the total duct length by 1 metre.
• A 45° bend reduces the total duct length by 0.5 metres.
• The first 90° bend is not included when calculating the maximum available length.

10.2 SEPARATE DUCTS

This type of installation makes it possible to discharge exhaust
fumes both outside the building and into single flue ducts.
Comburent air can be drawn in at a different location from that
of the flue terminal. The accessory splitting kit comprises a flue
duct adaptor Ø 110 mm (B) and an air duct adaptor Ø 110 mm
(A). For the air duct adaptor, fit the screws and seals previously
removed from the cap.
The 90° bend is used to connect the boiler to the inlet and
outlet ducts, adapting them to various requirements. It can also
be used as a supplementary curve combined with a duct or a
45° bend.
• A 90° bend reduces the total duct length by 0.5 metres.
• A 45° bend reduces the total duct length by 0.25 metres.
• The first 90° bend is not included when calculating the maximum available length.
27
∆P (Pa)
1.90 MP
320
1.110 MP
370
7104645.02 (1-01/12)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Luna duo-tec mp 1.110

Tabla de contenido