SILENSYS ADVANCED HEAT RECOVERY
INSTALLATION INSTRUCTIONS
• Check all cable glands for tightness before starting up the unit.
See appendix 5.
6.7. Filter drier
Silensys® Advanced condensing units are all fitted with a brazed filter
drier.
Replacement filter drier selection:
When changing the filter drier, ensure that it is replaced with an
equivalent in capacity and pressure drop and with the correct direction
of flow.
6.8. Safety devices
Pressure switch
The pressostat fitted in the unit is specific to run with the
authorised A2L refrigerants. Specifications:AC-15:10 A / 250 V AC
In case of replacement, consider the current, the technology of cut
out, of the model installed by Tecumseh in the Silensys® Advanced unit.
It is essential to keep the original wiring (relay function).
The pressure setting made by the manufacturer must be controlled and
adjusted to be in accordance with the local regulation in force.
Compressor compartment Panel fan
Air flow goal is to evacuate the refrigerant out of the compressor
compartment in case of leakage, to shorten the time of flammable
refrigerant presence around electrical components.
A permanent control is necessary. In case of fan failure, the unit
automatically stop.
While maintenance and commissioning check that the compressor
compartment panel fan is working, otherwise flammable refrigerant
presence is possible in the unit.
This fan has been sized to ensure efficient dilution of A2L refrigerant in
the event of a leak. It is essential to replace it with an original model.
Connections are available to provide an alarm. Refer to scheme in
appendix 7.
7. DISASSEMBLY AND DISPOSAL
Do
not
dispose
of
these
Equipment containing electrical components must not be disposed of
with household waste. It must be collected separately from electrical
and electronic waste in accordance with current local legislation.
Dispose of the condensing unit, compressor, oil and refrigerant in
accordance with local regulations.
8. WARRANTY
For information concerning the condensing unit warranty, please refer
to our general terms and conditions of sale
9. DECLARATION OF CONFORMITY
Silensys® Advanced condensing units comply with the Low
Voltage
Directive
2014/35/EU,
Directive 2014/68/EU and the Machinery Directive 2006/42/EC.
Certificates
of
conformity
www.tecumseh.com and on request.
14 • www.tecumseh.com
products
in
the
environment.
the
Pressure
Equipment
are
available
10. DECLARATION OF INCORPORATION
Only qualified staff are authorized to work on the condensing unit. This
product is defined as for installation in machines according to European
Directive 2006/42/CE.
It is not permitted to run the condensing unit before the machine
into which it is incorporated has been declared in conformance with
the pertaining legislation. The condensing unit itself is therefore not
required to comply with Directive 2006/42/CE.
In its constant endeavor to improve its products, Tecumseh EUROPE
SALES AND LOGISTICS S.A.S. S.A. reserves the right to change any
information in this instruction manual without prior notification.
Silensys® Advanced and L'Unite Hermétique® are registered trademarks
of Tecumseh EUROPE S.A.S.
at

Publicidad

loading