RS-485 Modbus master, LED3
1
2
3
4
1 s
Pos. Colour
1
-
Pulsating red
2
(single pulse)
3
Permanent red
4
Flashing green
Related information
6.1 Connecting the power supply
8.1 LED1 and LED2 remain off when the power
supply is connected
8.2 LED2 for internal communication is flashing red
8.3 LED2 for internal communication is permanently
red
8.4 LED1 is flashing yellow
8.5 LED3 for RS-485 interface is flashing red
10
3 s
Description
RS-485 is not used: LED
is off
RS-485 Modbus RTU
(Master): communication
failure
RS-485 Modbus RTU
(Master): configuration
error
RS-485 Modbus RTU
(Master):
Modbus is sending
or receiving data
4. Installation requirements
WARNING
Electric shock
Death or serious personal injury
Connect the CIM 290 only to a
Grundfos host product with a dedicated
CIM interface.
Installation must be carried out by
qualified and trained experts.
4.1 Security
The CIM module provides a secure way of performing
cellular data transmission to the cloud. It uses
encryption and mutual authentication based on X.509
certificates for access authentication. The CIM
module does not accept any incoming connection
attempts from the cellular network.
The CIM module acts as fieldbus master for the
GENIbus and Modbus RTU protocols. These
protocols use the underlying RS-485 communication.
As this does not have any built-in security, it is highly
recommended to allow physical access to the
installation to authorized personnel only, and
otherwise adhere to the initiatives suggested in the
local risk assessment if available.
4.2 RF safety
Installers and end users must be provided
with these installation and operating
instructions and operating conditions for
satisfying RF exposure compliance.
WARNING
Radiation
Minor or moderate personal injury
The antenna used for the product in
which the CIM module is fitted must be
installed with a separation distance of
at least 20 cm (0.66 feet) from
persons, and must not be co-located or
operated in conjunction with any other
antenna or transmitter.
Interference of other electronic equipment may occur
if the equipment is inadequately protected.