8.5 LED3 for RS-485 interface is flashing
red
Cause
Communication to
Modbus RTU slaves is
not working.
Related information
3.6 LEDs
8.6 No data is coming from the product
Cause
The SIM card is
dislocated.
The antenna conditions
are not optimal.
Other faults.
Related information
4.3 External cellular antenna requirements
Remedy
Make sure that
the slaves have unique
Modbus RTU
addresses.
Check the Modbus
RTU parameter
settings, such as baud
rate, parity bits, start/
stop bits.
There is no cloud
driver for the Modbus
RTU slave device
loaded to the CIM
module.
Remedy
Reinsert the SIM card
into the SIM slot.
The slanted edge of
the SIM card must
point upwards.
Improve the antenna
conditions. See section
Antenna requirements.
Contact Grundfos.
8.7 No BLE connection between the CIM
module and the smart phone
Cause
Bluetooth is
unresponsive on your
mobile phone.
BLE connection error.
Remedy
Disable and enable
Bluetooth again.
Delete the Grundfos
product from the
Bluetooth list on your
mobile phone and pair
it again.
Restart the Grundfos
product.
Update BLE firmware
to the latest version to
fix this
issue permanently.
Firmware upgrades for
specific products are
being prepared,
contact Grundfos for
more details.