• PARTIAL OPENING (except for ELA version)
Partial opening during normal operation (winter).
• CHEMIST'S OPENING (except for ELA version)
The door opens by the width set for chemist's opening (only works with ma-
nual key-opening pushbutton which, when the door is open, also controls
closing). The automatic closing operation is excluded.
• INTERNAL RADAR
It only activates the internal radar. The door opens when detecting one-way
transit.
• SECURITY DOOR RADAR
It activates the security door function.
• RESET
If you keep the key pressed for approximately 3 seconds and then release
it, you reset the default configuration, and exit from the user's menu.
LED blinking confirms that resetting has taken place.
If you do not execute any operation within the 10 seconds following the
entry of the user code, you come out of the user menu.
20.3) Modification of user code on PFD model selector
The default code is set as 12345. To modify it, press the T6 key for 15 sec.;
the red LEDs blink together. On entering the 5-figure code in use (T1 to T5
associated with respective numerical characters from 1 to 5), the red LEDs
switch off (one by one) and the corresponding green LEDs switch on, from
the top downwards, to confirm that the code is being completed.
If the code is exact, the 5 red LEDs start blinking again, and the new code
can be entered.
If the code is incorrect, press the T6 key for 15 sec. again and repeat the
operation.
At this point, the new code is memorised.
To access the user functions, see paragraph 20.2 "User functions of the
PFD selector".
20.4) Installer menu, modification of LINEA operational parameters
through the PFD mod. selector
Bring the DIP1 to the ON position to enable memory writing.
Remember to bring it to the OFF position at the end of programming.
When the T6 and T7 keys are pressed (per 10sec.), the L11 and L12 LEDs
start to blink at the same time as all the red LEDs, allowing the INSTALLER
CODE to be entered (the default code is 55555). After entering is comple-
ted, if the code is exact, you can access the operational parameter menu;
if the code is incorrect, you need to press the T6 and T7 keys again for 10
sec. and retype the code.
If the code is correct, all the LEDs go off except for L1, which stays on be-
cause modifications start from the TCA (automatic closing time) parameter,
associated with the L1 LED. Alternatively, the percentage of the parameter
value (with respect to full scale) is displayed over a bar of 10 LEDs (from
LED1 to LED10). Therefore you will see the L1 (TCA) LED, and then the va-
lue referring to the full scale of 60 seconds (the default value of 3 seconds
corresponds to the L12 LED, the lowest, which blinks).
If you do not execute any operation during the 120 seconds following the
installer code entry, you come out of the configuration menu.
The keys take on the following meaning:
T1 + (increases parameter value)
T2 - (decreases parameter value)
T3 RESET DEFAULT Keep the button pressed until a prolonged sound is
heard.
T4 CONFIRM (records parameter value)
T5 SUBSEQUENT PARAMETER (used to cyclically scroll parameters)
T6 EXIT (exits menu).
26 -
LINEA 1-2 - Ver. 02
INSTALLATION MANUAL
T7 PARAMETERS/LOGICS (used to move from parameter menu to logic
menu).
Set the required value using the T1(+) and T2(-) keys, the increase in
value is displayed through progressive lighting of the LED bar.
At the bottom and top ends of the range admitted for that parameter,
the board emits a long beep.
Use the T4 key to confirm the value set.
Move to the subsequent parameter using the T5 key (after reaching the
last parameter L9, you return to the L1 parameter).
To restore the default settings for parameters and logics, keep the T3
key pressed for 10 sec. (until the end of the acoustic signal), then dis-
connect and reconnect the mains power supply (and the battery, if fit-
ted).
Functional parameter sequence:
The default value is highlighted between [ ].
• LED 1 red:
• Green LED 2:
Red LED 3:
• Green LED 4:
• Red LED 5:
Green LED 6:
• Red LED 7:
• Green LED 8:
• Red LED 9:
• Green LED 10:
WARNING: Check that the impact force value measured at the
points established by the EN 12650-2 standard is lower than that
specified in the EN 12650-1 standard.
* In the case where, due to installation conditions, the door cannot reach
the programmed speed, the control function proceeds to reducing the pro-
grammed speed once every 10 manoeuvres until the maximum value is
reached. This operation takes place separately for the closing and opening
speed, and in certain cases may require a new learning cycle.
20.5) Installer menu, LINEA logic modification through the PFD mod.
selector.
The factory-preset value is highlighted between [ ].
• Enter the installer code by simultaneously pressing T6 and T7 for 10s
(see paragraph 20.4)
• Press T7, L12 comes on and stays on, this way you access the logic
menu.
• T1 activates the logic (LED on), T2 excludes the logic (LED blinking).
Waiting time on opening (TCA) [4s]
Regulates the value of automatic closing time from 1
to 60 seconds.
Speed on opening * [50%]
Regulates the value of opening speed from 0 to 99%
(from 30 to 90 cm/s for each leaf).
Increase this parameter to increase the opening
speed.
Speed on closing * [50%]
Sets the numerical value of closing torque from 0 to
99%, associated with the closing speed (from 10 to 35
cm/s for each leaf). Increase this parameter to increa-
se the closing speed.
Partial opening value [50%]
Regulates the percentage of partial opening (from
10% to 70%) with respect to total opening.
Chemist's opening value [25% for each leaf]
Opening dimension in %, from 0% (5cm) to 99% (30
cm) for each leaf, for the door in chemist's function.
Clearance time [30s]
Sets the required time (from 1s to 99 s). Activate the
manual key-opening command for the door to open
and stay open for the clearance time set.
Motor torque [25%]
Regulates the value of motor torque from 0 to 99%,
associated with the obstacle detection sensitivity
(from 1 to 5 kg). Increase this parameter to decrease
obstacle sensitivity.
Zone [1]
Sets the zone number (from 0 to 7) of the door inclu-
ded in the serial connection for centralised commands
(see fig. 27). The number of LEDs lit progressively in-
dicates the zone number set (the selected area 0 cor-
responds to none of the lit LEDs), starting from LED
12 (zone 1) as far as LED 6 (zone 7).
Zones 0 to 7 can be set through PFD, if a greater num-
ber of zones needs to be set, UNIPRO must be used.
End-of-run speed [10%]
Regulates the percentage of end-of-run speed (from
0% to 99%) at the mechanical opening and closing
stop plates (from 5 to 8 cm/s for each leaf).
Braking [80%]
Regulates the braking force (da 0% a 99%).