BFT LINEA 1 Instrucciones De Uso Y De Instalacion página 27

Automatizaciones para puertas
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 44
• T4 confirms the setting, T5 proceeds to setting the subsequent logic.
• T6 is used to come out of the installer menu.
The keys take on the following meaning:
T1
ON (activates logic)
T2
OFF (excludes logic)
T4
CONFIRM (records logic value)
T5
SUBSEQUENT LOGIC (used to cyclically scroll logics)
T6
EXIT (exits menu)
T7
PARAMETERS/LOGICS (used to move from parameter menu to logic
menu).
Operation logic sequence :
• Red LED 1:
Antipanic battery [On]
on: when the supply mains is disconnected, the door
opens and stays open (this does not happen if the
DAB1 device is not fitted or the night function is on).
blinking: when the mains is disconnected, the door
operates regularly if supplied with DAB1. Executes
learning after the first command. If the battery charge
falls below the minimum threshold, the door opens and
stays open (unless the night function is on).
• Green LED 2:
type of locking [blinking]
on: magnet
blinking: click
Electric lock on closing [Blinking]
• Red LED 3:
on: activates the electric lock before closing. Useful for
fitting the electric lock with the door open.
blinking: lock active on opening only.
• Green LED 4:
TCA active [On]
on: executes automatic door closing after the preset
dwell time
blinking: excludes automatic closing.
• Red LED 5:
Pre-alarm [Blinking]
on: the beep sound is activated each time the door
moves.
blinking: excludes beep sound.
• Green LED 6:
Lock hold [Blinking]
on: continuous lock. Keeps the electric lock activated
for 20s after the latest manoeuvre. Function advisable
for doors subject to intense traffic.
blinking: click lock. Activates the electric lock at each
opening for 2s.
• Red LED 7:
ram blow [on]
on: carries out ram blow
blinking: excludes ram blow
• Green LED 8:
disengages the electric lock [on]
switched on: electric lock disengaged
blinking: electric lock operates normally.
20.6) Modification of installer code on PFD mod. selector
The default factory code is set as 55555. To modify it, press the T7 key for
20 sec., and the red LEDs will blink together. On entering the 5-figure code
in use (T1 to T5 associated with respective numerical characters from 1
to 5), the red LEDs switch off (one by one) and the corresponding green
LEDs switch on, from the top downwards, to confirm that the code is being
completed. If the code is exact, the 5 red LEDs start blinking again to insert
the new code. After entering is completed, if the code is correct, you can
access the operational parameter menu; if the code is incorrect, you need
to press the T7 key again for 20 sec. and retype the code.
21) PROGRAMMING GETLIGHT PARAMETERS AND LOGIC DIP SWIT-
CHES THROUGH UNIPRO PROGRAMMER
The control unit, compatible with the eelink protocol, is supplied with ope-
ration parameters set by the manufacturer. The predefined parameters can
be changed through the UNIPRO programmer. Before modifying the para-
meters, carefully read the instructions relating to UNIPRO and proceed as
follows:
• connect the UNIPRO programmer to the control unit by means of the
UNIFLAT accessory (see fig.25). Open the "CONTROL UNITS" menu,
then the "PARAMETERS" submenu, and scroll the display screen pages
using the up/down arrows to set the numerical values of the parameters
listed below. For the operation logic, refer to the "LOGIC" submenu.
Here follows the meanings and the values which can be taken on by each para-
meter. The predefined parameter is the one given between square brackets [ ]:
• Automatic closing time [4s]
Set the numerical value of the automatic closing time (TCA) from 1 to 60
seconds.
INSTALLATION MANUAL
• %Motor torque [25%]
Set the numerical value of the motor torque from 0 to 99%, associated
with obstacle detection sensitivity (from 1 to 5 kg). Increase this parame-
ter to decrease obstacle sensitivity.
• %Opening torque * [50%]
Set the numerical value of the opening torque from 0 to 99%, associated
with opening speed (from 30 to 90 cm/s for each leaf). Increase this pa-
rameter to increase the opening speed.
• %Closing torque * [50%]
Set the numerical value of the closing torque from 0 to 99%, associated
with the closing speed (from 10 to 35 cm/s for each leaf). Increase this
parameter to increase the closing speed.
• %Braking [80%]
Set the numerical value for braking from 0 to 99%. Any increase in this
parameter increases the braking force during the shift from ordinary
speed to end-of-run speed.
• Clearance time [30s]
Set the required time (from 1s to 99 s). When the manual key-opening
command is activated, the door opens and stays open for the clearance
time set.
• Advanced parameters
address 1 [1] Sets the zone number (from 1 to 127) of the door inclu-
ded in the serial connection for centralised commands (see fig. 30).
address 2 [50%] Regulates the percentage of partial opening (from
10% to 70%) with respect to total opening.
address 3 [25% for each leaf] Opening dimension in %, from 0%
(5cm) to 99% (30cm) for each leaf, for the door in chemist's function.
address 4 [10%] Percentage of end-of-run speed at the mechanical
opening and closing stop plates (from 5 to 8 cm/s for each leaf).
WARNING: Check that the impact force value measured at the
points established by the EN 12650-2 standard is lower than that
specified in the EN 12650-1 standard.
* If, due to installation conditions, the door cannot reach the programmed
speed, the control unit proceeds to reducing speed every 10 manoeuvres
until it reaches the programmed speed. This operation takes place separa-
tely for the closing and opening speed, and in certain cases may require a
new learning cycle.
Logics:
• TCA active [1]
• Pre-alarm [0]
• Lock hold [0]
• Type of locking [0]
•Ram blow [1]
Advanced logics:
• Address 11: Antipanic battery [1]
• Address 12: Electric lock on closing [0]
•Address 13: disengages the electric lock [0]
1: executes automatic door closing after the dwell time
preset.
0: excludes automatic closing.
1: the beep sound is activated each time the door
moves.
0: excludes beep sound.
1: Continuous lock. Keeps the electric lock activated for
20s following each detection of transit. Function advisab-
le for doors subject to intense traffic.
0: Click lock. Activates the electric lock for 2s each time
the door opens.
1: Magnet
0: by click
1: Before carrying out the opening manoeuvre, the door
pushes in the closing direction for about 2 seconds. This
allows the electric lock to be released more easily.
0: Excludes the ram blow.
1: when the supply mains is disconnected, the door
opens and stays open (this does not happen if the DAB1
device is not fitted or the night function is on).
0: when the mains is disconnected, the door operates
regularly if supplied with DAB1. Executes learning after
the first command. If the battery charge falls below the
minimum threshold, the door opens and stays open (un-
less the night function is on).
1: Activates the electric lock before closing. Useful for
fitting the electric lock with the door open.
0: lock active on opening only.
1: The electric lock remains excluded (open), it only
ENGLISH
27
LINEA 1-2 - Ver. 02 -

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Linea 2

Tabla de contenido