AC supply voltage and frequency
Input displacement factor (cos φ)
Nominal motor power - kW
Nominal motor power - hp
Output voltage and frequency
100% RMS output current - A
150% overload current for 60 secs - A
Typical full load input current - A*
Typical inrush current - A** (duration <10ms)
Drive power losses at 480Vac at 6kHz switching
frequency - W
Weight - kg/lb
Cooling fan fitted
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Recommended input supply fuse - A
Control cable
Recommended input cable
Recommended motor cable
Recommended braking resistor cable
Minimum braking resistor value - Ω
Recommended braking resistor value - Ω
Resistor peak power rating - kW*
* Based on recommended braking resistor value.
** Absolute minimum braking resistor value.
Before fitting a braking resistor please read the information on Braking, and the
NOTE
Warnings on High Temperatures and Overload Protection at the end of this
section.
14
MODEL
Table 3.15 Commander SE Size 3, 400V units
MODEL
Table 3.16 Recommended fuses and cables
MODEL
**
Table 3.17 Braking Resistors
www.controltechniques.com
SE33400...
550
3 phase 380 to 480V +/-10%, 48 to 62Hz
5.5
7.5
3 phase, 0 to input voltage, 0 to 1000Hz
13.0
19.5
13.0
190
SE33400...
550
16
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
SE33400...
550
Commander SE User Guide
750
>0.97
7.5
10.0
16.5
24.8
15.4
80
270
6 / 13.2
Yes
750
20
>0.5
20
2.5
12
2.5
12
2.5
12
750
39.0
50
13.8
Issue Number 9