Parameter 5 set to A1.Pr
Local voltage (A1) speed reference input with 3 preset speeds
Close terminals 12 and 13 as in the following table to select the desired preset speed.
Terminal 12
Terminal 13
open
closed
open
closed
If Enable negative preset speeds (parameter 17) is set, then a negative preset
NOTE
speed will cause the motor to run in the reverse direction. Alternatively, closing
terminal 11 (Run Reverse) instead of terminal 10 will change the sign of the
selected speed such that a positive preset speed will become negative for reverse
rotation.
Parameter 5 set to A2.Pr
Remote current (A2) speed reference input with 3 preset speeds.
Close terminals 12 and 13 as in the following table to select the desired preset speed:
52
Figure 6.4 Terminal connections
Enable
open
closed
open
closed
closed
closed
closed
closed
Figure 6.5 Terminal connections
www.controltechniques.com
Run Forward
closed
closed
Preset speed 2 (parameter 12)
closed
Preset speed 3 (parameter 13)
closed
Preset speed 4 (parameter 14)
Speed reference
Local speed ref. (A1)
Commander SE User Guide
Issue Number 9