11.2.3 Commander SE Size 3, 200V product
Conformity
The drive conforms to UL listing requirements only when the following is observed:
•
UL listed class J 35A fast acting fuses e.g. Gould Amp-Trap A4J35, Littelfuse Power
Gard JLS35 or equivalent are used in the AC supply.
11.2.4 Commander SE Size 3, 400V product
Conformity
The drive conforms to UL listing requirements only when the following is observed:
•
UL listed class CC fast acting fuses e.g. Bussman Limitron KTK series, Gould Amp-
Trap ATM series or equivalent are used in the AC supply.
11.2.5 Commander SE Size 4
Conformity
The drive conforms to UL listing requirements only when the following is observed:
•
UL listed class J 40A fast acting fuses e.g. Gould Amp-Trap A4J40, Littelfuse
Power-Gard JLS40 or equivalent are used in the AC supply.
11.2.6 Commander SE Size 5
Conformity
The drive conforms to UL listing requirements only when the following is observed:
•
The drive is installed in a Type 1 enclosure, or better, as defined by UL50
•
UL listed class RK1 600Vac fuses are used in the AC supply
11.2.7 Commander SE RFI Filters
All recommended filters for Commander SE are UL recognised components, including
for Canada (CUL), under file number E64388.
Commander SE User Guide
Issue Number 9
www.controltechniques.com
77