10.4 Triggering Thresholds and Tripping Time
Rated power fre-
quency
60 Hz
Rated grid volt-
Triggering
age
threshold - Trig-
gering voltages
240 V
50 %
88 %
110 %
120 %
Measuring precisions:
• Triggering threshold: ±2% of the rated grid voltage
• Tripping time: ±1% of the nominal tripping time
• Triggering frequency: ±0.2% of rated power frequency
10.5 General Data
Width x height x depth
Weight
Length x width x height of the packaging
Transport weight
Operating temperature range
Storage temperature
Max. permissible value for relative humidity
(condensing)
Installation Manual
Triggering threshold Triggering frequency Tripping time
> 60.5 Hz
< 57 Hz to 59.8 Hz
(Standard: 59.3 Hz)
< 57.0 Hz
Triggering volt-
age - Neutral
conductor
57.6 V to 62.4 V 115.2 V to
103.2 V to
108.0 V
129.6 V to
134.4 V
141.6 V to
146.4 V
60.45 Hz to 60.55 Hz max. 0.1602 s
56.95 Hz to 59.85 Hz
(Standard: 59.25 Hz
to 59.35 Hz)
56.95 Hz to 57.05 Hz max. 0.1602 s
Triggering volt-
age - L1 and L2
124.8 V
206.4 V to
216.0 V
259.2 V to
268.8 V
283.2 V to
292.8 V
535 mm x 730 mm x 198 mm
(21.1 in x 28.7 in x 7.8 in)
26 kg (57.32 lbs)
800 mm x 600 mm x 300 mm
(31.5 in x 23.6 in x 11.8 in)
30 kg (66.14 lbs)
-25°C to +60°C (-13°F to +140°F)
-40°C to +60°C (-40°F to +140°F)
100 %
SBSxx-US-10-IA-xx-14
10 Technical Data
Adjustable: 0.16 s to
300 s
(Standard: max.
0.1602 s)
Tripping time
max. 0.1602 s
max. 2.002 s
max. 1.001 s
max. 0.1602 s
73