10 Technical Data
10.1 DC/AC
10.1.1 Sunny Boy Storage 3.8-US / 5.0-US
AC connection
Rated power
Maximum apparent AC power
Rated grid voltage
AC voltage range
Nominal AC current
Maximum output current during
stand-alone mode
Total harmonic factor of output
current
Maximum residual output cur-
rent
Duration of the maximum resid-
ual output current
Line synchronization character-
istics/inrush current
Rated grid frequency
Limits of accuracy of voltage
measurement
Limits of accuracy of frequency
measurement
Limits of accuracy of time mea-
surement at nominal trip time
Limits of accuracy of current
measurement
Limits of accuracy of power (ac-
tive/reactive) measurement
Limits of accuracy of power fac-
tor measurement
Installation Manual
SBS3.8-US-10
3800 W
3800 VA
240 V
211 V to 264 V
15.8 A
20 A
< 4 %
198 Apeak
33 ms
Method 2/18.5 A
60 Hz
2% of the AC voltage
±0.1 Hz
± 0.1 %
1% of the AC current
5% of the nominal AC power
0.01
10 Technical Data
SBS5.0-US-10
5000 W
5000 VA
240 V
211 V to 264 V
21 A
28 A
< 4 %
198 Apeak
33 ms
Method 2/18.5 A
60 Hz
2% of the AC voltage
±0.1 Hz
± 0.1 %
1% of the AC current
5% of the nominal AC power
0.01
SBSxx-US-10-IA-xx-14