Aventics PROFINET VS series Instrucciones De Servicio página 79

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 169
2
1
Fig. 6:
Replacing a multipole plug module with a bus coupler
AVENTICS | PROFINET | R412023897–BDL–001–AA
1. Unscrew the three screws (1) that fit the multipole plug
module (2) to the valves (hexagonal head, wrench size
8 mm).
2. Detach the module from the valve subbase (3).
3. Push the replacement bus coupler onto the tie rods (4) of the
valve unit. Make sure that the seal (5) is fitted correctly.
4. Refit and tighten the three screws (1).
Tightening torque: 2.8 to 3.2 Nm.
5. Make all the settings on the bus coupler (see "Making
settings" on page 65).
6. Connect the electrical connections to the bus coupler (see
"Connecting the module electrically" on page 61).
7. Check the section "PLC configuration of the CL03 valve
system" on page 70 and adjust the configuration if
necessary.
3
4
5
79
Replacement

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cl03Cl03-xl