Loading Device Master Data; Transferring The Configuration To The Controller; Assigning Names, Ip Addresses, And Subnet Masks - Aventics PROFINET VS series Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 169
AVENTICS | PROFINET | R412023897–BDL–001–AA
7.2.1

Loading device master data

The GSDML file with texts in English and German for the
bus coupler, series CL03 for PROFINET, is located on the
provided CD R412018133. The file can also be downloaded
from the AVENTICS Media Directory.
Each valve system is equipped with a bus coupler and valves,
depending on your order. The GSDML file contains the data that
needs to be assigned by the user in the data area of the
controller. The GSDML file is loaded in a configuration program,
which allows the user to set the parameters.
O
To configure the valve system PLC, copy the GSDML file on
CD R412018133 to the computer containing the PLC
configuration program.
You can use PLC configuration software from various
manufacturers for the PLC configuration. The descriptions in
the following sections therefore focus on the basic procedure
for configuring the PLC.
7.2.2
Transferring the configuration to the
controller
Data may be transferred to the controller once the system is
completely and correctly configured.
1. Make sure that the controller parameter settings are
compatible with those of the valve system.
2. Establish a connection to the controller.
3. Transfer the valve system data to the controller. The precise
process depends on the PLC configuration program.
Observe the respective documentation.
7.2.3
Assigning names, IP addresses, and subnet
masks
The bus coupler in the PROFINET network needs a clear name
in order to be recognized by the controller.
Commissioning and Operation
71