Class 2 Status Codes; Class 3 Status Codes - Fronius Symo 10.0-3 208-240 Manual De Instrucciones

Inversores para instalaciones fotovoltaicas acopladas a la red
Ocultar thumbs Ver también para Symo 10.0-3 208-240:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Class 2 Status
Codes
Code
Description
212
Overvoltage on L1
213
Undervoltage on L1
222
Overvoltage on L2
223
Undervoltage on L2
232
Overvoltage on L3
233
Undervoltage on L3
240
Arc detected
241
Arc detected
242
Arc detected
245
Arc Detector self-test failed
Arc Detector current sensor
247
faulty
249
Arc Detector faulty
*) If status code persists: Contact a Fronius-trained service technician
**) Fault is corrected automatically. If this status code keeps recurring, contact your system
installer
Class 3 Status
Class 3 comprises status codes that may appear during feed-in operation and that do not
Codes
cause a permanent interruption of the operation of feeding energy into the grid.
After automatic disconnection from the grid and waiting for its conditions to return to those
stipulated, your inverter will try to resume feed-in operation.
Code
Description
301
Overcurrent (AC)
302
Overcurrent (DC)
303
Overtemperature DC module
304
Overtemperature AC module
Behavior
Grid conditions are being test-
ed and as soon as they are
within the permissible range
again, the inverter will resume
feeding energy into the grid.
The status code is displayed
for approx. 4 seconds
Status code 241 is displayed
immediately after 240. The in-
verter disconnects from the
grid for safety reasons.
Status code 242 is displayed
immediately after status code
241 is reset.
The inverter disconnects from
the grid.
The inverter disconnects from
the grid.
Behavior
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Remedy
Check grid connections;**)
-
Before an inverter can be reset
following a detected electric
arc, check the entire affected
photovoltaic system for dam-
age.
Reset the status code by
pressing the "Enter" key.
Reset the status code by
pressing the "Enter" key.
The inverter restarts feeding
energy into the grid.
**)
Carry out AC reset;
The test is repeated. *)
*)
Remedy
*)
Purge cooling air open-
ings and cooling ele-
ments; **)
51

Publicidad

Tabla de contenido
loading

Tabla de contenido