Installation and Connection
The setting of the braking actuation voltage is also performed on the CDB1 board;
however, by means of the DIP switch S2. The values of voltage levels are presented
in table 3.4. As factory default, the braking actuation voltage is 20 % above the link
rated voltage.
Table 3.4: Setting of S2 (fine tuning of the braking voltage)
Braking Actuation Voltage (according to the model and setting of S1)
Braking Actuation Voltage Fine
Tuning (according to the model and
setting of S2)
Position S1
S2:1 S2:2 S2:3 S2:4 380 400-415 440-480 500-525 550-575 600
ON
0
OFF OFF OFF OFF
1
2
3 4
ON
1
ON OFF OFF OFF
1
2
3 4
ON
2
OFF ON OFF OFF
1
2
3 4
ON
3
ON
1
2
3 4
ON
4
OFF OFF ON
1
2
3 4
ON
5
ON OFF ON
1
2
3 4
ON
6
OFF ON
1
2
3 4
ON
7 ON
(*)
1
2
3 4
ON
8
OFF OFF OFF
1
2
3 4
ON
9
ON OFF OFF
1
2
3 4
ON
10 OFF ON OFF
1
2
3 4
ON
11 ON
1
2
3 4
ON
12 OFF OFF ON
1
2
3 4
ON
13 ON OFF ON
1
2
3 4
ON
14 OFF ON
1
2
3 4
ON
15 ON
1
2
3 4
(*)
Factory setting.
26 | DBW03
0
588
592
596
ON OFF OFF
600
OFF
604
OFF
608
ON
OFF
612
ON
ON
OFF
(*)
(*)
(*)
616
ON
641
ON
667
ON
691
ON OFF
ON
716
ON
741
ON
766
ON
ON
791
ON
ON
ON
Position S1
1
2 / 3
0
644
717
816
648
722
821
652
728
826
656
733
831
660
738
836
664
744
841
668
749
846
754
672
(*)
851
689
760
871
706
765
891
723
771
911
740
776
931
757
781
951
774
787
971
791
792
991
SLAVE
1
2
3
690
890
930 1069
896
936 1076
902
942 1083
908
948 1090
914
954 1097
920
960 1104
926
966
1111
972 1118
932
(*)
940
975
1128
948
978
1138
956
981
1148
964
984 1158
972
987 1168
980
990
1178
988
993 1188