Micropulse Linear Transducer - Rod Style
7
Calibration procedure (cont.)
Move magnet to new desired
start position.
New start
value
Null point
Move magnet to new
end position
before
after
Fig. 7-4: Manual adjust procedure
7.3

Manual adjust

This method allows you to set a
new start and/or end value. This
may be useful if the magnet can not
be brought to the null or end point
of the transducer.
To do this, the magnet is brought
alternately to the new start and end
before
position, and the displayed values
are adjusted by keystroke or press-
after
ing the buttons until the desired
values are reached.
➥ ➥ ➥ ➥ ➥ Section 9 Manual adjust mode
New end
value
End
point
Ignition Class "n"
7.4

Reset

The reset function can be used to
restore the transducer to its factory
default settings.
➥ ➥ ➥ ➥ ➥ Section 10 Resetting all values
(Reset)
7.5

Online-setting

Setting the start and end values is
done while the system is running.
➥ ➥ ➥ ➥ ➥ Section 11 Online setting mode
english
9