BTL5-A/C/E/G1_-M_ _ _ _-B/Z-NEX-S32/KA_ _
Micropulse Linear Transducer - Rod Style
4
Wiring (cont.)
When routing the cable between
the transducer, controller and
power supply, avoid proximity to
high voltage lines to prevent noise
coupling. Especially critical is in-
ductive noise caused by AC har-
monics (e.g. from phase-control
devices), against which the cable
shield provides only limited protec-
tion.
Cable length max. 20 m; Ø 6 to
8 mm. Longer lengths may be used
if construction, shielding and routing
are such that external noise fields
will have no effect on signal integrity.
BKS connector, view
towards solder side of
female BKS-S32M-00
or BKS-S33M-00
Fig. 4-2: Pin assignments BKS,
connector type BTL
Output signals
Pin
Cable
BTL5-A11
1
YE
yellow
not used
2
GY
gray
0 V
3
PK
pink
10...0 V
4
not used
5
GN
green
0...10 V
Supply voltage (external)
Pin
Cable
BTL5-A/C/E/G1_
6
BU
blue
GND
7
BN
brown
+24 V
8
WH
white
do not connect
Table 4-1: Wiring
6
english
right-angle BKS-S33M-00
No. 99-5672-78-08 (Binder part no.)
straignt BKS-S32M-00
No. 99-5672-19-08 (Binder part no.)
Fig. 4-3: Connector (optional)
-C10
-C17
➀
0...20 mA
20...0 mA
not used
not used
➁
-E10
-E17
4...20 mA
20...4 mA
➀
➀
➀
GND on the control side, but they
must never be connected to the
shield.
➁
voltage and EMC!
Ignition Class "n"
-G11
➀
not used
10...–10 V
–10...10 V
Unused leads can be tied to
Reference GND for supply