Shielding And Cable Routing - Balluff BTL7 Serie Manual De Instrucciones

Ocultar thumbs Ver también para BTL7 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BTL7-A/C/E/G501-M _ _ _ _ -P-S32/S115/KA _ _
Magnetostrictive Linear Position Sensor – Profile Style
4
Installation and connection (continued)
4.5

Shielding and cable routing

Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the BTL and controller using a shielded cable.
Shield: Braided copper shield with minimum 85%
coverage.
Connector version: Shield is internally connected to
connector housing.
Cable version: On the BTL side the cable shielding is
connected to the housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL and strong, external magnetic fields.
Cable routing
Kabel zwischen BTL, Steuerung und Stromversorgung
nicht in der Nähe von Starkstromleitungen verlegen
(induktive Einstreuungen möglich).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-A/G
Max. 30 m
BTL7-C/E
Max. 100 m
Prerequisite: Construction, shielding and routing preclude the effect of any
1)
external noise fields.
Tab. 4-5:
Cable lengths BTL7
Noise elimination
To avoid equipotential bonding - a current flow - through
the cable shield, please note the following:
Use insulating bushes
Put the control cabinet and the system in which the
BTL is located to the same ground potential.
12
english
1)
1)

Publicidad

Tabla de contenido
loading

Tabla de contenido