Short circuit current rating
Suitable for use on a circuit capable of delivering not more than 200,000 rms symme-
trical amperes when protected by 600 V non-semiconductor fuses or 500 V minimum
inverse time circuit breakers.
Suitable for motor group installation on a circuit capable of delivering not more than
5,000 rms symmetrical amperes when protected by maximum 40 A, 600 V non-semi-
conductor fuses or 500 V minimum 40 A maximum inverse time circuit breaker.
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
The table below list the permitted maximum branch circuit protection:
Series
MOVIGEAR
Motor overload protection
MOVIGEAR
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 150% of the rated motor current.
Ambient temperature
MOVIGEAR
output current. To determine the output current rating at temperatures above 40  °C,
the output current should be derated by 3.0% per K between 40 °C and 55 °C.
An additional speed-dependent derating may be required. For details, refer to chapter
"Technical data and dimension sheets".
Wiring diagrams
For wiring diagrams, refer to chapter "Electrical installation".
®
MOVIGEAR
, the max. voltage is limited to 500 V.
®
MOVIGEAR
, the max. voltage is limited to 500 V.
®
®
is provided with load and speed-sensitive overload protection and ther-
®
is suitable for an ambient temperature of 40 °C, max. 55 °C with derated
Non-semiconductor
fuses
40 A/600 V
Instrucciones de funcionamiento – MOVIGEAR
Instalación eléctrica
Normas de instalación
Inverse time circuit
breakers
500 V minimum/
40 A maximum
®
-DAC-B
5
85