ALARM MESSAGES

ALARM MESSAGES
ALARM MESSAGES
ALARM MESSAGES
Alarms may be rearmed either automatically or manually. The following Alarm Messages may
appear on the screen:
Serious Error
Power Failure
Serious Error
Thermal Motor
Serious Error
High Pressure
Serious Error
Low Pressure
Serious Error
Probe Failure W
Serious Error
Probe Failure CO
Serious Error
Probe Failure EV
Serious Error
Probe Failure EN
Serious Error
Flow Failure
Serious Error
Repeated Failure
Serious Error
Fan Failure
Serious Error
4WV Failure
© ASTRALPOOL 2015 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT
System power failure.
The order of the three phases is inverted.
Automatically and immediately rearms when the problem is solved.
The thermal circuit is open. Failure in the thermal system.
Semi-automatically rearmed when the problem is solved and the MODE
key is pressed.
The high pressure switch indicates the circuit is open.
Pressure is too high.
Semi-automatically rearmed when the problem is solved and the MODE
key is pressed.
The high pressure switch indicates the circuit is open.
Pressure is too low.
Semi-automatically rearmed when the problem is solved and the MODE
key is pressed.
Failure in the water sensor reading.
Automatically and immediately rearms when the problem is solved.
Failure in the condenser sensor reading.
Automatically and immediately rearms when the problem is solved.
Failure in the evaporator sensor reading.
Automatically and immediately rearms when the problem is solved.
Failure in the ambient sensor reading.
Automatically and immediately rearms when the problem is solved.
No water flow.
Automatically and immediately rearms when the problem is solved.
If there is a failure in the thermal sensor or the pressure switches, retry
up to three times daily.
Manual rearming with technical assistance.
The equipment checks fan operation. If the fan does not work properly,
the unit stops. Semi-automatic rearm: every 30 minutes the unit will try
to start working again.
The equipment checks the 4 way valve whenever it has to be engaged. If
it is not working properly, the unit stops. Semi-automatic rearm: every 30
minutes the unit will try to start working again.
.