Filling, Topping Up The Heating System - Daikin EHSX04P30D Instrucciones De Instalación Y Mantenimiento

Ocultar thumbs Ver también para EHSX04P30D:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 261
7
Inspection and maintenance
INFORMATION
If the storage tank temperature falls below specific min-
imum values, the safety settings of the Daikin Altherma
EHS(X/H) prevent the heat pump from being operated at
low outside temperatures:
- Outside temperature < -2 °C, minimum storage tank tem-
perature = 30 °C
- Outside temperature < 12 °C, minimum storage tank tem-
perature = 23 °C
Without backup heater:
The storage tank water must be heated to the required
minimum storage tank temperature with an external heater
booster.
With backup heater (EKBUxx):
At an outside temperature of < 12 °C and a storage tank
temperature of < 35 °C, the backup heater (EKBUxx) is
automatically switched on to heat the storage tank water to
at least 35 °C.
▪ To speed up the heating process with the backup
heater, temporarily set the [Config. of external heat
source] parameter = "1" and [Ext. hot water power] para-
meter to the maximum value of the backup heater
[→ Main menu → Settings → Ext. Source].
▪ Select the [1x Hot Water] parameter in the "User" menu
and switch it on. After the heating has completed, switch
off the parameter again [→ Main menu → User → 1x
Load].
Without installed
solar system
1
Connect the filling hose with non-return valve (1/2") to the
"Solar - inflow" connection
2
Fill the storage tank of the Daikin Altherma EHS(X/H) until wa-
ter escapes from the overflow connection
3
Remove the filling hose with non-return valve (1/2").
With installed
solar system
1
Install the filling connection with combined filling and draining
valve (accessory KFE BA) following the solar control and pump
unit (EKSRPS4).
2
Connect the filling hose with non-return valve (1/2") to the pre-
viously installed combined filling and draining valve.
3
Fill the storage tank of the Daikin Altherma EHS(X/H) until wa-
ter escapes from the overflow connection
4
Remove the filling hose with non-return valve (1/2").
Installation and maintenance instructions
38
(Fig.
7-1, item 1).
(Fig.
7-1, item 23).
(Fig.
7-1, item 23).
Fig. 7-1
Filling the buffer tank - without connected DrainBack
solar system
Item
Designation
1
Solar - inflow
23
Safety overflow
Tab. 7-1
7.2.2

Filling, topping up the heating system

DANGER: RISK OF ELECTROCUTION
During the filling process, water can escape from any leak-
ing points and can cause an electric shock if it comes into
contact with live parts.
▪ Before the filling process, de-energise the Daikin
Altherma EHS(X/H).
▪ After the first filling and before switching on the Daikin
Altherma EHS(X/H) at the mains switch, check whether
all electric parts and connection points are dry.
WARNING
Polluted domestic water is hazardous to health.
▪ When filling the heating system, make sure that heating
water cannot flow back into the domestic water pipe.
Daikin Altherma EHS(X/H)
Daikin Altherma integrated solar unit
008.1444099_00 – 07/2018 – EN