11.3.1 Error type A or D
1
2
3
4
Fig. 41: Error type A, diagram
1
2
3
4
5
6
8
Fig. 42: Error type D, diagram
6.0.0.0
E000
6.0.0.0
1/1
6.0.0.0
1/1
Fig. 43: Acknowledge error type A or D
Installation and operating instructions SIE - DIE
7
60
S
0
12.3
S
Error type A (Fig. 41):
Program
Contents
step/query
1
• Error code is displayed
• Motor off
• Red LED on
• SSM is activated
• Error meter is increased
2
> 1 minute?
3
Error acknowledged?
4
End; auto control is continued
Yes
No
Error type D (Fig. 42):
Program
Contents
step/query
1
• Error code is displayed
• Motor off
• Red LED on
• SSM is activated
2
• Error meter is increased
3
Is there a new type "A" error?
4
> 1 minute?
5
Error acknowledged?
6
Is there a new type "A" error?
7
Branching for error type "A"
8
End; auto control is continued
Yes
No
If type A or D errors occur, proceed as follows to acknowledge
(Fig. 43):
• To change to the menu mode, press the acknowledge button.
The menu number <6.0.0.0> flashes.
• Press the acknowledge button again.
The menu number <6.0.0.0> is displayed statically.
The time remaining until the error can be acknowledged is displayed.
• Wait until the remaining time is up.
The time till manual acknowledgement is always 60 seconds for error
types A and D.
• Press the acknowledge button again.
The error is acknowledged and the status page is displayed.
English
81