4 Installing the inverter
4.4
Minimum clearances
75
B + 124
24
4.5
▶
75
4.6
1.
2.
3.
Condition: The load-bearing capacity of the wall is sufficient
B + 124
▶
▶
Requirements for the installation site
Ensure that the following requirements are satisfied:
–
The minimum clearances have been maintained
–
The direct current cable can be laid from the photo-
voltaic modules to the inverter
–
The alternating current cabling can be laid to the
meter cabinet
–
The installation site is fixed, vertical and level
–
The installation site is not exposed to direct sunlight
when installing on an external wall
–
The immediate installation environment is difficult to
ignite
–
The installation site is free from continuous vibrations
–
The installation site meets the requirements of cli-
mate class 4K4H in accordance with IEC 60721-3-4
–
An Internet router is available for using the web portal
–
The data connections for connecting other approved
products can be laid to the inverter
Wall-mounting the product
Check the load-bearing capacity of the wall.
Note the total weight of the product.
Only use fixing material that is permitted for the wall.
Use a spirit level to align the mounting plate horizontally
on the wall, as shown in the figure.
Use four screws to secure the mounting plate to the wall.
Installation and maintenance instructions VPV I 0020273427_02