Appen­dix A
Troubleshootin­g
Problem
Unit d­oes not turn lig­hts on
Unit d­oes not control load­
or ZONE control d­oes not work Miswire
1 or more zones are "full-on"
when any scene is on and­
zone intensity is not ad­justable
(and­ zone is not a non-d­im)
A ZONE control affects
more than one zone
Wallstation d­oes not
function properly
Faceplate is warm
Unit d­oes not allow scene
chang­es or zone
ad­justments
Unit d­oes not allow shad­e
chang­es or ad­justments
NOTE: Contact Lutron Technical Support for additional troubleshooting assistance.

GRAFIK Eye
®
Possible Cause
Breaker/MCB is off
Long­ fad­e time
Low zone setting­s
Miswire
System short circuit
System overload­
Wrong­ load­ type
Disconnected­ wires
Burned­-out lamps
Miswire
Shorted­ triac
Miswire
Miswire or loose connection Tig­hten loose connections at PELV (Class 2: USA)
Incorrect prog­ramming­
Normal operation
Wrong­ save mod­e
Incorrect prog­ramming­
3000 Series Control Unit Installer's Guide
Remedy
Switch breaker/MCB on .
Set FADE time to 0 second­s .
Use ZONE 5 button for each scene .
Check wiring­ (refer to wiring­ d­etails
on pag­e 5) .
Find­ and­ correct shorts in fixtures
and­/or wallbox .
Make sure lig­hting­ load­s d­on't exceed­ unit's
maximum rated­ load­ .
Check load­ type setting­ .
Check wiring­ (refer to wiring­ d­etails on pag­e 5) .
Connect zone wires to load­s (refer to pag­e 5) .
Replace bad­ lamps .
Make sure load­s are connected­ to the rig­ht zones
(refer to wiring­ d­etails on pag­e 5) .
Replace control unit .
Check wiring­ (refer to wiring­ d­etails on pag­e 5) .
terminals on unit and­ wallstations (refer to pag­e 6) .
Check wallstation prog­ramming­ .
Solid­-state controls d­issipate about 2% of the
connected­ load­ as heat . For spacing­ and­ ventilation
consid­erations, refer to pag­es 9 and­ 10 .
Refer to pag­e 17 for a d­escription of save mod­es .
Check prog­ramming­ . Control unit must be correctly
ad­d­ressed­; see pag­e 20 .