Setting Up System Communications - Lutron Grafik Eye 3000 Serie Guia Del Instalador

Ocultar thumbs Ver también para Grafik Eye 3000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25

Setting Up System Communications

If your GRAFIK Eye 3000 Series lighting system has more than one control unit, you need
to address the control units and then set up communications between the control units,
wallstations, and other optional accessories.
NOTE: A single control unit operating shade zones must also be addressed.
Checking System Interconnections
Before you address and set up communications between control units, make sure your system
interconnections are working.
To check system interconnections:
1. Select scene 1 (press the top SCENE button) on
one of the control units.
2. Is scene 1 selected on all other control units?
• If yes, the PELV (Class 2: USA) wiring is
correct and you can begin addressing the
control units.
• If no, the GRAFIK Eye control unit has been
addressed to other than A- (factory default).
See below for more information on addressing
control units.
-or-
PELV (Class 2: USA) is miswired. Check for
loose connections, shorted or crossed links.
Assigning an Address to Each Control Unit
If your lighting system has multiple control units, assign a unique system address (A1 through
A8) to each control unit. Once any control unit has been addressed, communication is lost
between all other components until each control unit has been addressed. To program a
wallstation, refer to its documentation.
NOTE: A single control unit operating shade zones must also be addressed.
ZONE 5
ZONE 6
3
Assign a
unique address
20
GRAFIK Eye
®
2
A-
Select
FADE
TEMPORARY
ZONES
M S
MASTER
3000 Series Control Unit Installer's Guide
Press SCENE 1 button . . .
. . . all other SCENE 1 LEDs light
To address each control unit:
1. Enter setup mode. Press and hold the
SCENE 1 and OFF buttons for about
three seconds, until the scene LEDs
cycle.
2. Select A-. Press the FADE  button
until A- (the factory default address)
displays in the FADE window.
3. Assign a unique address. Press the
MASTER  button once; the next "free"
1
4
,
(unassigned) address automatically
Enter (exit)
displays in the FADE window. This will
setup mode
be the control unit's address. (If you are
working on the first control unit in the
lighting system, A1 will display.)
4. Exit setup mode. Press and hold the
SCENE 1 and OFF buttons for about
three seconds, until the LEDs stop
cycling.
5. Repeat steps 1 through 4 for each
control unit.
R

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido