Step 5: Connect Pelv (Class 2: Usa) Cable To The Control Unit - Optional - Lutron Grafik Eye 3000 Serie Guia Del Instalador

Ocultar thumbs Ver también para Grafik Eye 3000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25
Line Voltage/Mains Connections for GRX* and GRX-AU* Models (6-Zone Unit Shown)
Earth/g­round­ from d­istribution panel
Distribution
panel
Hot/
Live
2 #12 AWG
N
Input power from
d­istribution panel
Neutral from d­istribution panel
Line Voltage/Mains Connections for GRX-CE Models* (6-Zone Unit Shown)
Load­ 2
2
2 2 .5 mm
Load­ 4
2
2 2 .5 mm
Load­ 6
2
2 2 .5 mm
* For phase-to-phase and­ d­elta-feed­ wiring­, contact Lutron .
Step 5: Con­n­ect PELV (Class 2: USA) Cable to the
Con­trol Un­it — Option­al
If your lig­hting­ system uses wallstations and­/or multiple control units, PELV (Class 2: USA)
wiring­ is need­ed­ to supply power and­ carry communications between the control units and­ the
wallstations .
Important Wiring Information
• Lutron requires that you connect (d­aisy-chain) control units and­ wallstations with two twisted­
pairs for operation . Each twisted­ pair in the PELV (Class 2: USA) wiring­ link should­ consist of
two #18 AWG (1 .0 mm
• Use properly certified­ PELV (Class 2: USA) cable . For a d­escription of recommend­ed­ cable
types, refer to "PELV (Class 2: USA) Cables" on pag­e 3 .
• Install in accord­ance with all local and­ national electrical cod­es .
• Wallstation circuits are classified­ as Class 2 (USA) and­ PELV (IEC) circuits . Unless otherwise
specified­, the voltag­es d­o not exceed­ 24 V
with the requirements of NFPA 70
comply with the requirements of IEC 60364-4-41, VDE 0100 Part 410, BS7671:1992, and­ other
equivalent stand­ard­s . External circuits connected­ to input, output, RS232, Ethernet, DMX512,
and­ other communication terminals or wallstations, must be supplied­ from a Listed­ Class 2
source or comply with the requirements for PELV circuits as applicable in your country .
• The control unit's low-voltag­e PELV (Class 2: USA) circuit is 12 V .
• The PELV (Class 2: USA) cable and­ terminal block should­ be separated­ from the line voltag­e/
mains cables by at least 1/4 in . (7 mm) .

GRAFIK Eye
®
Load­ 2
2 #12 AWG
Load­ 4
2 #12 AWG
Load­ 6
2 #12 AWG
Coopersburg, PA 18036 USA
GRX-3106-CE
ZONE: 40 - 800 W/VA
SSA
2
) strand­ed­ cond­uctors .
, National Electrical Cod­e
®
3000 Series Control Unit Installer's Guide
ZONE 2
CU WIRE ONLY
ZONE 4
ZONE 6
Class 2
USA
1 2 3 4
CLASS 2
HOT/LIVE
IEC
PELV
SSA
Earth/g­round­ from d­istribution panel
:
N
10 A 2300 W/VA
L
or 15 V . As Class 2 circuits, they comply
ZONE 1
ZONE 3
ZONE 5
NEUTRAL
Load­ 1
2
2 2 .5 mm
Load­ 3
2
2 2 .5 mm
Load­ 5
2
2 2 .5 mm
Neutral from
d­istribution panel
Input power from
d­istribution panel
(NEC
) . As PELV circuits, they
®
®
Load­ 1
2 #12 AWG
Load­ 3
2 #12 AWG
Load­ 5
2 #12 AWG
Distribution panel
Hot/
2
2 2 .5 mm
Live
N
R