Control program
t
5s
circuit to be checked at atmospheric pressure
4
t
7.5s
Time between start-up and "AR" main relay excitation
6
t
22.5s
1st check phase with atmospheric pressure
1
t
5s
Put gas circuit to be checked under pressure
3
t
27.5s
2nd check phase with gas pressure
2
t
67.5s
Total duration of seal test, up to burner operation consensus
5
t
22.5s
Return to the programmer stand-by position = preset for a new check.
20
Program execution
AL remote alarm signal
AR main relay with the 'ar...' contacts
AS device fuse
BR shut-down relay with 'br...' contacts
DW external pressure switch (leak test)
EK reset key
GP external pressure switch (of system gas pressure)
HR reset relay with 'hr...' contacts
L1 device fault warning light
SK line switch
I... XI
33 / 44
0006080103_201309
programmer cam contact
Activated terminals of
equipment or electric
connections