Generator Sizing - Franklin Electric SubDrive15 Manual De Uso

Ocultar thumbs Ver también para SubDrive15:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Table 2: Maximum Motor Cable Length (in feet)
Franklin Electric
Controller Model
Motor Model
SubDrive15
234 514 xxxx
SubDrive20
234 315 xxxx
SubDrive30
234 316 xxxx
214 505 xxxx
214 507 xxxx
MonoDrive
214 508 xxxx
214 508 xxxx
MonoDriveXT
224 300 xxxx
224 301 xxxx
NOTE: 1 ft = 0.305 m
A 10-foot (3.05 m) section of cable is provided with the SubDrive/MonoDrive to connect the pressure sensor.
NOTE:
Maximum allowable wire lengths are measured between the controller and motor.
Aluminum wires should not be used with the SubDrive/MonoDrive.
All wiring to comply with the National Electrical Code and local codes.
MonoDrive minimum breaker amps may be lower than AIM Manual specifications for the motors listed
due to the soft-starting characteristic of the MonoDrive controller.
SubDrive minimum breaker amps may appear to exceed AIM Manual specifications for the motors listed
because SubDrive controllers are supplied from a single-phase service rather than three-phase.
Motor Overload Protection Note: The drive electronics provide motor overload protection by preventing
motor current from exceeding the maximum Service Factor Amps (SFA). Motor overtemperature sensing
is not provided by the drive.

Generator Sizing

Basic generator sizing for the Franklin Electric SubDrive/MonoDrive system is 1.5 times maximum
input watts consumed by the drive, rounded up to the next normal-sized generator.
Recommended minimum generator sizes:
MonoDrive
1/2 hp = 2000 Watts (2 kW)
3/4 hp = 3000 Watts (3 kW)
1 hp = 3500 Watts (3.5 kW)
MonoDriveXT
1.5 hp = 4000 Watts (4 kW)
2 hp = 5000 Watts (5 kW)
SubDrive15 = 3500 Watts (3.5 kW)
SubDrive20 = 5700 Watts (6 kW)
SubDrive30 = 7000 Watts (7 kW)
Note: Not to be used on a Ground Fault Circuit Interrupter (GFCI). If using an externally regulated generator,
verify that the voltage, Hertz and idle speed are appropriate to supply the drive.
AWG Copper Wire Sizes, 167
HP
14
1.5 (1.1 kW)
420
2.0 (1.5 kW)
320
3.0 (2.2 kW)
240
0.5 (0.37 kW)
400
0.75 (0.55 kW)
300
1.0 (0.75 kW)
250
1.0 (0.75 kW)
250
1.5 (1.1 kW)
190
2.0 (1.5 kW)
190
SubDrive/MonoDrive
F (75
o
12
10
8
670
1060
-
510
810
1000
390
620
990
650
1020
-
480
760
1000
400
630
990
400
630
990
310
480
770
250
390
620
C) Insulation
o
6
4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1000
-
970
-
19

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Subdrive20Subdrive30MonodriveMonodrivextNema 3r

Tabla de contenido