Drive Wiring

s
WARNING
!
Serious or fatal electrical shock may result from failure to connect the motor, the SubDrive/
MonoDrive, metal plumbing, and all other metal near the motor or cable to the power supply
ground terminal using wire no smaller than motor cable wires. To reduce risk of electrical
shock, disconnect power before working on or around the water system. Do not use motor
in swimming areas.
1. Verify that the power has been shut off at the main breaker.
2. Verify that the dedicated branch circuit for the SubDrive/MonoDrive is equipped with a
properly-sized circuit breaker. (See Table 1, pg. 18 for minimum breaker size.)
3. Use appropriate strain relief or conduit connectors. See below for conduit hole and
knockout sizes.
22,2
[
0.88
28.6 KNOCKOUT
[1.13]
22,2
KNOCKOUT
[0.88]
110,7
97,7
[4.36]
[3.85]
47,7
[1.88]
33,6
[1.32]
40,3
[1.59]
4. Remove the SubDrive/MonoDrive lid.
5. Feed the motor leads through the opening on the bottom right side of the unit and
connect them to the terminal block positions marked
Yellow and Black.
HOLE
]
82,3
[3.24]
198,3
[7.81]
SubDrive/MonoDrive
12,7
HOLE
[0.5]
(Green Ground Wire), Red,
28,6 HOLE
[1.13]
34.9 KNOCKOUT
[1.37]
97,7
[3.85]
27