Before Test Run
Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with
500V megaohm meter and check if the resistance is above 1M*. It can't be operated if it is below
1M*.
Connect it to the power supply of outdoor units to energize the heating belt of the compressor.
To protect the compressor at startup, power it on 12 hours prior to the operation.
Check if the arrangements of the drainpipe and connection line are correct.
The drainpipe shall be placed at the lower part while the connection line placed at the upper part.
Heat preservation measures should be taken such as winding the drainpipe esp. in the indoor
units with heating insulating materials.
The drain pipe should be made a slope type to avoid protruding at the upper part and concaving
at the lower part on the way.
Checkup of Installation
check if the mains voltage is matching
check if there is air leakage at the piping joints
check if the connections of mains power and indoor & outdoor units are correct
check if the serial numbers of terminals are matching
check if the installation place meets the requirement
check if there is too much noise
check if the connecting line is fastened
check if the connectors for tubing are heat insulated
check if the water is drained to the outside
check if the indoor units are positioned
Ways of Test Run
Do ask the installation personnel to make a test run. Take he testing procedures according to
the manual and check if the temperature regulator works properly.
When the machine fails to start due to the room temperature, the following procedures can be
taken to do the compulsive running. The function is not provided for the type with remote control.
Set the wired controller to refrigerating/heating mode, press "ON/OFF" button for 5 seconds to
enter into the compulsive refrigerating/heating mode. Repress "ON/OFF" button to quit the
compulsive running and stop the operation of the air conditioner.