2. Mechanical and electrical
installation
WARNING!
It can be extremely dangerous to touch
the electrical parts even when the mains
supply has been disconnected.
Wait at least 4 minutes after the input
power has been removed before servicing
the CU 321.
For outdoor installation, the CU 321 must
be installed in a minimum NEMA 3R enclo-
sure with provisions for heating and venti-
lating designed to keep the CU 321 within
its operating temperature limits.
2.1 Mechanical installation (3 hp, 1-/3-ph, and 5 hp, 3-ph)
All dimensions are in inches.
Fig. 6
Dimensional sketch of CU 321 (without the NEMA 1 kit)
Spacing
If more than one CU 321 is installed, the following
must be observed during mechanical installation.
IMPORTANT
The CU 321 is cooled by air circulation. For proper
cooling, allow a minimum of 4 inches (100 mm) of
open space above, below and beside the CU 321
to protect the unit from overheating.