5. INSTALLATION OF BATTERY POWER DEVICE
5.1 Fix inside automation, on left side, the battery power device.
5.2 Connect the battery power device to the BAT connector of the
electronic control, using the supplied cable.
5.3 Ensure that the battery is connected to the electronic board.
8.4 Connect the automation to the power supply and wait at least 30
minutes to let the battery recharge. Make sure that removing the power
supply, the door is working with battery power device, in mode choice
using the BTMD menu.
Note: to allow recharging, the battery power device must always be
connected to the electronic control. In case of long periods of inactivity of
the automatic door, disconnect the battery from the electronic board.
5.5 If desired, you can connect a LED to signal the presence of the battery
(not supplied) between the terminals [+] and [LD] as shown in the figure. In
the presence of mains power, the LED makes a blink every 10 seconds,
while in the absence of mains power, the LED remains lit.
5.6 In the absence of mains power, battery operation is disabled when the
charge level of the battery is too low.
If desired, you can connect a N.O. contact to reactivate the battery
operation (example a key switch, not supplied) between the terminals [+]
and [KY ] as shown in Figure.
FA00008-EN v.7 – 05/2017
14
CAME S.p.A.