Battery Extensions For Ups Backup Times Up To 60 Minutes; Cla Module (Long Backup Time Charger) For Backup Times From 2 To 8 Hours - Eaton EX RT 7 Manual De Instalación Y Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 156
Battery extensions for UPS backup times up to 60 minutes (at full load)
EX RT offers a standard backup time of 5/7 minutes at full load.
To increase backup time, it is possible to connect EX RT EXB 7/11 modules to the UPSs.
Battery extensions EX RT 7/11
EX RT 7
+ EX RT EXB 7
/
EX RT 11
+ EX RT EXB 11
7 kVA:
11 kVA:

CLA module (Long backup time charger) for backup times from 2 to 8 hours

(Part number 68004)
Very long backup times, from 2 to 8 hours at full load, require a EX RT CLA module.
~
EX RT CLA
Battery backup
time
2 hours
4 hours
8 hours
Total battery voltage : 240 V DC (20 x 12 V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalisation
section).
EX RT EXB 7
+
+
/
EX RT EXB 11
7 min
20 min
5 min
14 min
EX RT 7/11
Recommended batteries for:
EX RT 7
EX RT 11
65 Ah
100 Ah
130 Ah
200 Ah
260 Ah
400 Ah
EX RT EXB 7
EX RT EXB 7
+
/
/
EX RT EXB 11
EX RT EXB 11
32 min
45 min
22 min
30 min
5 0 A
1. Presentation
EX RT EXB 7
EX RT EXB 7
+
+
/
/
EX RT EXB 11
EX RT EXB 11
57 min
70 min
42 min
53 min
34007558EN/AE - Page 9

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ex rt 11Ex rt 5 3:1Ex rt 7 3:1Ex rt 11 3:1

Tabla de contenido