Connection of CLA module
Connect the battery cable
z
CLA module.
Connect the cable
z
Connect the battery:
z
- Cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
Use a circuit-breaker (curve B, 50 A) for cable protection.
z
Connect the input cable of the
z
- AC input cable cross-section (not provided) : 2,5 mm².
z
Use a circuit-breaker (curve C, 10 A) for cable protection.
BATTERY
_
+
AC INPUT
N
L
To battery
AC Input
(provided with the CLA module) between the power module and the
28
(provided with the CLA module) between the power module and the CLA module.
29
CLA module to the AC input:
2. Installation
29
28
34007558EN/AE - Page 25