Operation; Initial Start Up; Ups Personalisation; Accessing Personalisation With Front Panel Buttons - Eaton EX RT 7 Manual De Instalación Y Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 156

3. Operation

3.1 Initial start up

OFF

UPS personalisation

If specific settings are required, it is recommended to enter the UPS personnalisation mode at this stage.
It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for
Windows included in the EATON Solution-Pac power management suite CD-ROM.

Accessing personalisation with front panel buttons

OFF
Local settings
Function
Language
Date / time format
Date / time change
Audible alarm
Output features
Function
Output voltage
Frequency converter
Output frequency
Eco mode
Hot standby
Operating mode
Transfer on Bypass AC
source
Break time
Overload level
(*) : - Select "I/T Network" and "AC Bypass within tolerance" for computer loads.
- Select "Industrial" and "AC Bypass out of tolerance" in case of absolute need for service continuity
(with potential 10 ms break).
Page 26 - 34007558EN/AE
15
PRESS ON
TO START UPS
ON
UPS SET UP
EXIT ENT
ON
19
20
Factory setting
International format
(JJ-MM-AAAA/HH:MM)
Time in France
Quick beeps
Factory setting
230 Volts AC
Disabled
Auto ranging
Disabled
Disabled
Industrial
If the Bypass AC source
is out of tolerances
10 ms
102 %
Check that the manual bypass switch
Set the normal AC source switch
Set the battery circuit breaker
The load is powered via the bypass AC source, but not
protected by the UPS.
Batteries are recharging, an eight-hour recharge period is
necessary to get full backup time.
LED
15
is ON.
Press "scroll up"
z
19
together for more than 3 seconds.
Press the function button
z
enter the set up mode and follow the LCD messages using the
buttons now defined as select keys.
English
French, Spanish, German, Italian.
US format (MM-DD-YYYY/HH:MM AM/PM).
MM-DD-YYYY/HH:MM adjustable.
Options
200/208/220/240/250
Enabled
50/60 Hz
Enabled
Enabled
I/T Network
If the Bypass AC source
is inside tolerances.
10 to 200 ms
(by steps of 10 ms)
50/70 %
is on Normal position.
7
to the "I" position.
9
to the "I" position.
12
and "scroll down"
function buttons
20
placed under the ENT word to
20
Options
Slow beeps.
Comments
Bypass AC source disabled.
User selectable under
frequency converter mode.
See glossary.
N+1 redundancy (See section
2.5 "Hot standby").
(*)
(*)
Break time calibration during
load transfer on Bypass AC
source out of tolerances.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ex rt 11Ex rt 5 3:1Ex rt 7 3:1Ex rt 11 3:1

Tabla de contenido