Use the fuses and wire sizes listed up in the table below when wiring the main circuit. Make sure not to exceed the given tightening torque values.
Main
Model
Fuse
CIMR-VC
[Ferraz]
BA0001
TRS5R
BA0002
TRS10R
BA0003
TRS20R
BA0006
TRS35R
BA0010
TRS50R
BA0012
TRS60R
4A0001
TRS2.5R
4A0002
TRS5R
4A0004
TRS10R
4A0005
TRS20R
4A0007
TRS20R
4A0009
TRS20R
4A0011
TRS30R
4A0018
A6T50
4A0023
A6T60
4A0031
A6T70
4A0038
A6T80
<1> The leakage current of this drive exceeds 3.5 mA. Therefore according to IEC61800-5-1 a protective earthing conductor with a cross section of at least 10 mm
be used. Smaller protective earthing conductors can be used if automatic power supply interruption in case of discontinuity of the protective earthing conductor is provided.
<2> Use a ring terminal end to connect the ground wire to the ground terminal.
NOTICE: Equipment Hazard. Be sure to connect the recommended fuses between each input terminal and the main circuit power supply (3-phase: L1, L2, L3, single-phase:
L1, L2). As the V1000 Series IP66 Type enclosure is very compact, fuses are required to prevent serious damage to the drive components as well as prevent
personal injury in the event that a short-circuit occurs.
Tightening Torque Values
Tighten the main circuit terminals using the torque values provided by the table below.
Tightening Torque (Nm)
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below. For safe wiring it is
recommended to use solid wires or flexible wires with ferrules. The stripping length respectively ferrule length should be 8 mm.
Flexible with ferrule
YASKAWA Europe TOMP_C710606_75A V1000 IP66 - Quick Start Guide