Parámetros
4.8.4 8-4* Conf. protoc. FC MC
8-40 Selección de telegrama
Option:
Función:
Permite el uso de telegramas
configurables libremente o de
telegramas estándar para el puerto
FC.
[1]
Standard telegram 1
*
[300] Standard telegram
FCM300
8-42 Configuración de escritura PCD
Se pueden asignar diferentes parámetros a los PCD 3-10 de los
PPO. El número de PCD depende del tipo de PPO.
Los valores de los PCD de 3 a 10 se escribirán en los parámetros
seleccionados como valores de datos.
Option:
[0]
None
[1]
[302] Minimum Reference
[2]
[303] Maximum Reference
[3]
[341] Ramp 1 Ramp up time
[4]
[342] Ramp 1 Ramp down time
[5]
[351] Ramp 2 Ramp up time
[6]
[352] Ramp 2 Ramp down time
[7]
[380] Jog Ramp Time
[8]
[381] Quick Stop Time
[9]
[412] Motor Speed Low Limit
[Hz]
[10]
[414] Motor Speed High Limit
[Hz]
[11]
[590] Digital & Relay Bus
Control
[12]
[676] Terminal45 Output Bus
Control
[13]
[696] Terminal 42 Output Bus
Control
[14]
[894] Bus Feedback 1
[15]
FC Port CTW
[16]
FC Port REF
8-43 Config. lectura PCD
Se pueden asignar diferentes parámetros a los PCD 3-10 de los
PPO. El número de PCD depende del tipo de PPO.
Los PCD del 3 al 10 mantienen los valores de datos en tiempo
real de los parámetros seleccionados.
Option:
[0]
None
[1]
[1500] Operation Hours
[2]
[1501] Running Hours
[3]
[1502] kWh Counter
[4]
[1600] Control Word
[5]
[1601] Reference [Unit]
[6]
[1602] Reference %
[7]
[1603] Status Word
MG03N205
Guía de programación
8-43 Config. lectura PCD
Se pueden asignar diferentes parámetros a los PCD 3-10 de los
PPO. El número de PCD depende del tipo de PPO.
Los PCD del 3 al 10 mantienen los valores de datos en tiempo
real de los parámetros seleccionados.
Option:
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
Función:
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
[36]
4.8.5 8-5* Digital/Bus
Parámetros para configurar la unión del código de control
Digital/Bus.
8-50 Selección inercia
Option:
Función:
[0]
Entrada
digital
Danfoss A/S © 11/2015 Reservados todos los derechos.
[1605] Main Actual Value [%]
[1609] Custom Readout
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1615] Frequency [%]
[1616] Torque [Nm]
[1618] Motor Thermal
[1630] DC Link Voltage
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1638] SL Controller State
[1650] External Reference
[1652] Feedback [Unit]
[1660] Digital Input 18,19,27,33
[1661] Terminal 53 Switch Setting
[1662] Analog Input 53(V)
[1663] Terminal 54 Switch Setting
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1671] Relay Output [bin]
[1672] Counter A
[1673] Counter B
[1690] Alarm Word
[1692] Warning Word
[1694] Ext. Status Word
[1850] Sensorless Readout [Unit]
Función:
AVISO!
Este parámetro solo está activo si el
parámetro 8-01 Puesto de control se ajusta
como [0] Digital y cód. ctrl.
Seleccione el control de la función de inercia a
través de los terminales (entrada digital) y / o a
través del bus.
Activa la inercia a través de una entrada digital.
Función:
4
4
77