Automatic Calibration Procedure - Sime Brava One BF Manual De Instalación Y Mantenimiento

Calderas murales de baja temperatura
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
3.9

Automatic calibration procedure

This procedure MUST BE CARRIED OUT after replacing:
– the nozzles for gas conversion
– the gas valve following a fault
– the electronic board following a fault
and is necessary so that the new components can be identified
and can communicate with those already fitted on the boiler.
m
CAUTION
Considering that:
– the front panel has been removed, the control
panel has been brought forward and down and that
the points (6) and (7) of the gas valve have been
connected to the pressure gauges
– the main system switch must be set to "ON"
– the gas supply must be open
– there must be no current requests for heat
("Summer" mode
"Winter"
n
with air thermostats open)
– the adjustments described below must be carried out
in sequence.
6
Procedure valid for GAS CONVERSION
– go into the parameter section by pressing the buttons
and
o
(approximately 5 seconds) at the same time until
"tS"
(installer) appears on the 2 digits of the display which
alternate with "0.1" (parameter number) and a "2" (set value)
holding the buttons
>
NOTE:
scrolling movement. Pressing the button
scroll through the previous parameters.
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "0.3"
– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
l
with hot water valve closed or
7
Fig. 44
or
<
increases the speed of the
<
allows the user to
– press the button
>
and select "1" (LPG)
– press the button
o
modification. the value will stop flashing.
Procedure which MUST be carried out after:
– gas conversion
– changing the gas valve following a fault
– changing the the electronic board following a fault.
– go into the parameter section (if not already there) by pressing
the buttons
<
and
o
time until "tS" (installer) appears on the 2 digits of the display
which alternate with "0.1" (parameter number) and a "2" (set
value)
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "tS 4.9"
– press the button
o
access the default value which is flashing
<
– press the button
>
or
– press the button
o
stop flashing
– keep the button
>
pressed and scroll through the parameters
until reaching parameter "tS 7.0"
– press the button
o
access the default value which is flashing
for at least 3 seconds to confirm the
(approximately 5 seconds) at the same
to confirm (approximately 3 seconds) and
<
to set the value at "49"
to confirm the modification The value will
to confirm (approximately 3 seconds) and
87