Deleting one or more programmed actions
Deleting one or more programmed actions is done at the same time
as storing the programmed actions.
When all actions for one day have been programmed, make sure that
the display shows the highest action number you would like to save.
By pressing the < button for 5 seconds, you store all actions except
those with a higher action number than the one that is displayed.
E.g. when the < button is pressed when action number 3 is
displayed, actions 1, 2 and 3 are stored but 4 and 5 are deleted.
Deleting a mode
1
Press the < button to enter the programming/consulting mode.
2
Select the operation mode you would like to delete by means of
the pi and pj buttons.
The actual mode is blinking.
3
Press the < and ba button simultaneously for 5 seconds to
delete the selected mode.
Deleting a day of the week
1
Press the < button to enter the programming/consulting mode.
2
Select the operation mode you would like to delete by means of
the pi and pj buttons.
The actual mode is blinking.
3
Press the < button to confirm the selected mode.
The actual day is blinking.
Select the day you would like to delete by means of the pi
4
and pj buttons.
The selected day is blinking.
Press the < and ba button simultaneously for 5 seconds to
5
delete the selected day.

Operating the remote alarm option

An optional EKRP1HBA digital I/O PCB can be connected to the
indoor unit and be used to remotely monitor your system. This
address card offers 3 voltage free outputs:
Output 1 = THERMO ON/OFF
this output will be enabled when your unit is in space heating
operation.
Output 2 = ALARM OUTPUT
this output will be enabled when your unit is in error condition.
Output 3 = DOMESTIC HOT WATER MODE ON/OFF
this output will be enabled when your unit is in domestic water
heating operation.
For more details about the wiring connections of this option, refer to
the wiring diagram of the unit.

Operating the optional remote controller

If besides the main remote controller the optional remote controller is
installed as well, the main remote controller (master) can access all
settings while the second remote controller (slave) can not access
schedule settings and parameter settings.
Refer to the installation manual for more details.
RKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system and options
4PW55803-1

Field settings

The configuration of the Rotex system is done through field settings.
In this operation manual all field settings related to the operation of
the unit and user demand are explained. A list of all those field
settings and default values is given under "Field settings table" on
page 15. In this same list, we provided for 2 columns to register the
date and value of altered field settings at variance with the default
value.
For a total list of field settings, refer to the installation manual.
All field settings are accessible and programmable through the user
interface on the indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[5-03], which is indicated on the user interface display. The first digit
[5] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.

Procedure

To change one or more field settings, proceed as follows.
3
2
1
Press the z button for a minimum of 5 seconds to enter FIELD
SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).
Press the ébi button to select the appropriate field setting
2
first code.
3
Press the ébj button to select the appropriate field setting
second code.
Press the pfi button and pfj button to change
4
the set value of the select field setting.
5
Save the new value by pressing the pr button.
6
Repeat step 2 through 4 to change other field settings as
required.
7
When finished, press the z button to exit FIELD SET MODE.
Changes made to a specific field setting are only
NOTE
stored when the pr button is pressed. Navigating to a
new field setting code or pressing the z button will
discard the change made.
Before shipping, the set values have been set as
NOTE
shown under "Field settings table" on page 15.
When exiting FIELD SET MODE, "88" may be
displayed on the remote controller LCD while the
unit initializes itself.