Commissioning; Preliminary Operations; Before Commissioning - Sime BRAVA ONE OF ErP Serie Manual De Instalación Y Mantenimiento

Calderas murales de baja temperatura
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
3

COMMISSIONING

3.1

Preliminary operations

a
WARNING
– Should it be necessary to access the areas in the
bottom part of the appliance, make sure that the
system components and pipes are not hot (risk of
burning).
– Before replenishing the heating system, put on
protective gloves.
Before commissioning the appliance, check that:
– the type of gas is correct for the appliance
– the gas isolation valves for the heating system and the water
system are open
– the system pressure as shown on the pressure gauge when
the system is cold , is between 1 and 1.2 bar
– the pump impeller rotates freely.
3.2

Before commissioning

After having carried out the preliminary operations, perform the
following to start the boiler:
– set the main system switch to "ON"
ON
– the type of gas for which the boiler has been calibrated, "nG"
(methane) or "LG" (LPG,) will appear followed by the power.
After this the correct representation of the symbols will be
checked and finally "- -" will appear on the display
– press the button
"SUMMER mode"
detected at that moment will appear on the display
– open one or more than one hot water tap. The boiler will work
at maximum power until the taps are closed.
– if there is a fault, the message "AL" will appear on the display
followed by the fault code (eg. "06" - no flame detected).
Fig. 28
m
CAUTION
If the boiler has blocked, restore the start conditions
by pressing and holding the button
than 3 seconds. This operation can be carried out no
more than 6 times.
– close the taps opened previously and check that the appliance
shuts down
– press the button
value of the heating water temperature detected at that
moment will appear on the display
– adjust the air thermostat and check that the boiler starts and
operates correctly
– to check that the pressure in the network and the nozzles are
correct, the procedure described in section must be carried
out "Chimney sweeper function".
s
once for at least 1 second to select
l
. The value of the delivery sensor
o
(
s
once to select "WINTER mode"
R
) for more
n
. The
79

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Brava one 25 of erp

Tabla de contenido