Trip Curve
Courbe de déclenchement
Auslösekurve
Curva del disparo
COLD START
DEMARRAGE A FROID
KALTSTART
ARRANQUE EN FRIO
Class 10
1000
100
10
1
0.1
1
Multiple of FLA
Intensités pleine charge multiples
Short Circuit Ratings
Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No. 14
E1 Plus Cat. No.
Max. available fault
current (kA)
ED1AB, ED1BB, EEAB,
1
EEBB
ED1CB, ED1DB, ED1EB,
ED1ED, ED1FD
193, 193S
5
EECB, EEDB, EEEB, EEED,
EEFD, EEPB, EERB, EESB,
EETD
EEEE, EEFE, EEGE, EEUE,
10
EEVE
Table 3 Short Circuit Ratings per EN 60947-4-1
E1 Plus Cat. No.
Prospective S.C.
current, Ir (kA)
ED1AB, ED1BB, EEAB,
1
EEBB
ED1CB, ED1DB, EECB,
1
EEDB, EEPB, EERB
193,193S
ED1EB, EEEB, ED1ED,
ED1FD, EEED,
3
EEFD, EEEE, EEFE,
EESB, EETD
EEGE, EEUE, EEVE
5
Table 5 Overload relay only, High fault short circuit ratings per UL508 and CSA 22.2 No. 14
Max. available fault.
current (kA)
Cat. No.
ED1CB, ED1DB, ED1EB,
EECB, EEDB, EEEB
100
ED1ED, ED1FD, EEED,
193
EEFD
EEEE, EEFE, EEGE
Table 6 Fuse Selection Table Class gL/gG and Class aM Fusing
Motor
Recommended Fuse
1500 rpm
Type
Rated
Current
[kW]
[A]
[A]
0.06
0.24
Class gL/gG
2
0.09
0.33
Class gL/gG
2
0.12
0.43
Class gL/gG
2
0.18
0.61
Class gL/gG
2
0.25
0.8
Class gL/gG
4
0.37
1.1
Class gL/gG
4
0.55
1.5
Class gL/gG
6
0.75
1.9
Class gL/gG
6
1.1
2.7
Class gL/gG
10
1.5
3.5
Class gL/gG
10
2.2
5.0
Class gL/gG
16
3
6.6
Class gL/gG
20
4
8.5
Class gL/gG
25
5.5
11
Class gL/gG
32
7.5
15
Class gL/gG
40
10
20
Class gL/gG
50
11
22
Class gL/gG
63
15
29
Class gL/gG
80
18.5
36
Class gL/gG
80
22
41
Class gL/gG
100
30
56
Class gL/gG
125
37
68
Class gL/gG
160
45
81
Class gL/gG
160
41053-358-01
DIR 41053-358 (Version 09)
Curva de disparo
Curva di intervento
PARTIDA À FRIO
AVVIAMENTO A FREDDO
Class 15
1000
100
10
1
0.1
8
1
Múltiplo de FLA
Vielfache des FLA-Wertes
Table 2 Type I and Type II Fuse Coordination with Bul. 100-C contactors per EN 60947-4-1
Max. voltage (V)
S.C.P.D.
Suitable for use
with fuses only
600
Not resticted to
fusing only
193
Conditional S.C.
Max.
S.C.P.D.
current, Iq (kA)
voltage (V)
Suitable for use
with fuses only
100
690
Not resticted to
fusing only
Max. voltage (V)
UL class RK1 fuse (A)
60
600
100
200
Contactor
ED/EE O/L Relay
Type
Type
Thermal
Setting
[A]
100-C09
193-ED1AB
0.10 - 0.50
100-C09
193-ED1AB
0.10 - 0.50
100-C09
193-ED1AB
0.10 - 0.50
100-C09
193-ED1BB
0.20 - 1.0
100-C09
193-ED1BB
0.20 - 1.0
100-C09
193-ED1CB
1.0 - 5.0
100-C09
193-ED1CB
1.0 - 5.0
100-C09
193-ED1CB
1.0 - 5.0
100-C09
193-ED1CB
1.0 - 5.0
100-C09
193-ED1CB
1.0 - 5.0
100-C09
193-ED1DB
3.2 - 16
100-C09
193-ED1DB
3.2 - 16
100-C09
193-ED1DB
3.2 - 16
100-C12
193-ED1DB
3.2 - 16
100-C23
193-ED1DB
3.2 - 16
100-C30
193-EEED
5.4 - 27
100-C30
193-EEED
5.4 - 27
100-C30
193-EEFD
9 - 45
100-C37
193-EEFD
9 - 45
100-C43
193-EEFD
9 - 45
100-C60
193-EEGE
18 - 90
100-C72
193-EEGE
18 - 90
100-C85
193-EEGE
18 - 90
HOT START
DEMARRAGE A CHAUD
WARMSTART
ARRANQUE EN CALIENTE
Class 20
1000
100
10
1
0.1
8
1
Intensités pleine charge multiples
Multiplo di Max amp.
E1 Plus Cat. No.
Contactor Cat. No. Max. starter FLC
ED1AB, EEAB
100-C09
ED1BB, EEBB
100-C09
ED1CB, ED1DB, EECB,
100-C12
EEDB
100-C16
100-C23
100-C09
100-C12
ED1EB, EEEB
100-C16
100-C23
100-C30
ED1ED, ED1FD
100-C37
EEED, EEFD
100-C43
100-C60
EEEE, EEFE
100-C72
100-C85
100-C60
EEGE
100-C72
100-C85
EEVE
100-C97
Table 4 High Fault Short Circuit Ratings, using Fusing, per UL508 and CSA 22.2 No. 14
E1 Plus Cat. No.
ED1AB, EEAB
ED1BB, EEBB
ED1CB, ED1DB, ED1EB,
EECB, EEDB, EEEB
193
ED1ED, ED1FD
EEED, EEFD
EEEE, EEFE, EEGE
193-EEED or 193-EEFD with 100-C30, 100-C37 or 100-C43 contactor: 480V/65kA; 600V/30kA when protected by Allen-Bradley 140U-H6C3
followed by suffixes CB rated 50A max.
Motor
Recommended Fuse
Contactor
1500 rpm
Type
Rated
Type
Current
[kW]
[A]
[A]
0.06
0.24
Class aM
1
100-C09
0.09
0.33
Class aM
1
100-C09
0.12
0.43
Class aM
1
100-C09
0.18
0.61
Class aM
2
100-C09
0.25
0.8
Class aM
2
100-C09
0.37
1.1
Class aM
2
100-C09
0.55
1.5
Class aM
2
100-C09
0.75
1.9
Class aM
4
100-C09
1.1
2.7
Class aM
4
100-C09
1.5
3.5
Class aM
4
100-C09
2.2
5.0
Class aM
6
100-C09
3
6.6
Class aM
8
100-C09
4
8.5
Class aM
10
100-C09
5.5
11
Class aM
12
100-C12
7.5
15
Class aM
16
100-C16
11
22
Class aM
25
100-C30
15
29
Class aM
32
100-C30
18.5
36
Class aM
40
100-C37
22
41
Class aM
50
100-C43
30
56
Class aM
63
100-C60
37
68
Class aM
80
100-C72
45
81
Class aM
100
100-C85
(5)
PARTIDA À QUENTE
AVVIAMENTO A CALDO
Class 30
1000
100
10
1
0.1
8
1
Prospective S.C.
Conditional S.C.
Max. voltage
(A)
current, Ir (kA)
current, Iq (kA)
(V)
0.5
1
1
9
12
1
16
23
9
12
3
16
23
100
600
30
37
3
43
60
72
3
85
60
72
5
85
97
Max. starter FLC
Max.available
Contactor Cat. No.
fault current (kA) Max. voltage (V)
(A)
0.5
100-C09
1
100-C09
9
100-C12
12
100-C16
16
100-C23
23
100
100-C30
30
100-C37
37
100-C43
43
100-C60
60
100-C72
72
100-C85
85
ED/EE O/L Relay
Type
Thermal
Setting
[A]
193-ED1AB
0.10 - 0.50
193-ED1AB
0.10 - 0.50
193-ED1AB
0.10 - 0.50
193-ED1BB
0.20 - 1.0
193-ED1BB
0.20 - 1.0
193-ED1CB
1.0 - 5.0
193-ED1CB
1.0 - 5.0
193-ED1CB
1.0 - 5.0
193-ED1CB
1.0 - 5.0
193-ED1CB
1.0 - 5.0
193-ED1DB
3.2 - 16
193-ED1DB
3.2 - 16
193-ED1DB
3.2 - 16
193-ED1DB
3.2 - 16
193-ED1DB
3.2 - 16
193-EEFD
9 - 45
193-EEFD
9 - 45
193-EEFD
9 - 45
193-EEFD
9 - 45
193-EEGE
18 - 90
193-EEGE
18 - 90
193-EEGE
18 - 90
8
Type I Max. Class
Type II Max. Class
J or CC fuse (A)
J or CC fuse (A)
3
3
6
6
20
15
20
20
30
30
40
40
20
15
20
20
30
30
40
40
50
50
50
50
70
70
80
80
100
100
150
150
80
80
100
100
150
150
150
150
Max. UL Class J or CC
fuse, CSA HRCI-J (A)
3
6
20
20
30
40
600
50
50
70
80
100
150